Flexible metallic conduit systems

25

LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT SYSTEMS

— Low Fire Hazard EMI/EMC Screen liquidtight conduit systems Type EMILFH-SPL conduit

Advantages include: • EN45545-2 and BS EN 61386-1 & 23 accreditation • HL3 - R22 & R23 rating

The EMILFH-SPL conduit systems are a Low Fire Hazard Performance rated, flexible, liquidtight range. Designed to meet the demand for ‘interoperability’ and compliance with stringent local and European fire safety requirements in the rail infrastructure market, the EMILFH-SPL system, is accredited with the EN45545-2 standard achieving the highest HL3 fire performance rating for both interior and exterior locations. The system provides high performance levels of UV resistance working in a temperature range of (-20°C to +90°C). Providing outstanding performance for Surface Flammability, Smoke Generation Rate and Toxic Gas Generation, according to ASTM E 162, ASTM E 662 and Bombardier SMP 800-C testing procedures, covering fire safety requirements worldwide, thanks to its internal braiding, it is a very good solution where low smoke and toxicity are of concern and EMI/EMC screening is required.

• Up to IP69 rating • Medium flexibility • Suitable for Any buildings & infrastructure where low smoke, low toxicity and EMI screening is required, wide use underground and in any part of train vehicles and infrastructure • EMI/EMC screening

LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT SYSTEMS - TYPE LFH-SPL CONDUIT

— Liquidtight flexible metallic conduit systems Type EMI LFH-SPL conduit

Low fire hazard performance, under-braided, covered steel flexible conduit /Materials: Galvanised steel core, string packing up to 32mm, Interlocked core 40mm and above with galvanised steel overbraid; Low fire hazard jacket The NEW EMILF- SPL conduit systems are Low Fire Hazard Performance rated, flexible, liquidtight range. Designed to meet the demand for ‘interoperability’ and compliance with stringent local and European fire safety requirements in the rail infrastructure market, the EMILFH-SPL system, is accredited with the EN45545-2 standard achieving the highest HL3 fire performance rating for both interior and exterior locations. The system provides high performance levels of UV resistance w orking in a temperature ra nge of (- 2 0°C to + 90 °C) . Providing outstanding performance for Surface Flammability, Smoke Generation Rate and Toxic Gas Generation, according to ASTM E 162, ASTM E 662 and Bombardier SMP 800-C testing procedures, covering fire safety requirements worldwide , thanks to its internal braiding, it is a very good solution where low smoke and toxicity are of concern and EMI/EMC screening is required.

— Type EMILFH-SPL

Advantages include: • EN45545-2 and BS EN 61386-1 & 23 accreditation • HL3 - R22 & R23 rating

Nominal conduit size (mm)

Outside diameter (mm)

US conduit size (in)

Outside diameter (mm)

Inside diameter (mm)

Coil length (m)

• Up to IP69 rating • Medium flexibility • Suitable for Any buildings & infrastructure where low smoke, low toxicity and EMI screening is required, wide use underground and in any part of train vehicles and infrastructure • EMI/EMC screening

Part no.

EMILFH-SPL16/25M EMILFH-SPL20/25M EMILFH-SPL25/25M EMILFH-SPL32/25M EMILFH-SPL40/10M EMILFH-SPL50/10M EMILFH-SPL63/10M NEW

16 20 25 32 40 50 63

12 16 21 27 35 41 53

3/8 ½

17.9 21.3 26.5 33.2 42.0 48.0 60.5

12.3 15.8 20.8 26.5 35.0 40.0 51.3

110 130 160 200 250 290 360

¾ Low fire hazard performance , under-braided, covered steel flexible conduit / Materials: Galvanised steel core, string packing up to 32mm, interlocked core 40mm and above with galvanised steel overbraid; Low fire hazard jacket

1

Conduit size

Dimensions (mm)

US / CAN

1 1/4 1 1/2

Outside Dia. (A)

Inside Dia. (B)

Bend radi (C)

IEC/EN (mm)

in

mm

Part No.

EMILFH-SPL16 EMILFH-SPL20 EMILFH-SPL25 EMILFH-SPL32 EMILFH-SPL40 EMILFH-SPL50 EMILFH-SPL63

16 20 25 32 40 50 63

3/8" 1/2" 3/4"

12 16 21 27 35 41 53

17.9

12.3 15.8 20.8 26.5 35.0 40.0 51.3

110 130 160 200 250 290 360

21.3 26.5 33.2 42.0 48.0 60.5

2

Part number example: To order quote part number, colour & conduit coil length, e.g. EMIEF-SPL16/BL/25m.

1"

1 1/4" 1 1/2"

2"

Approvals

IP rating

Appropriate fitting

Temperature range UV resistance

Part number example: To order quote part number, colour & conduit coil length, e.g. EMILFH-SPL16/BL/25m

For use with: Type SPL, SSPL and SAM

Static applications: -20oC to +90oC Moving applications: --5oC to +105oC

High

Approvals

IP rating

Appropriate fitting

Temperature range UV resistance

IP66 IP67 IP68 IP69

Type M, C45 & C90 For use with: Type SPL, SSPL and SAM

Static applications: -20oC to +90o C Moving applications: -5oC to +105o C

High

Type A, B, M, C45 & C90 IP66

Type M, C45 & C90

Flexibility & fatigue life

IP67 IP68 IP69

Flexibility & fatigue life

Type A, B, M, C45 & C90

Type M, C45 & C90 (10 bar 30mins) NFPA130

Medium flexibility – Medium fatigue life Medium flexibility – Medium fatigue life

Type M, C45 & C90 (10 bar 30mins)

EN45545-2 HL3 - R22 & R23 ASTM E 162 ASTM E 662 Bombardier SMP 800-C

NSF 14159-1-2014 NSF 169-2009

Fire performance & EMI screen Self extinguishing Halogen free Fire performance & EMI screen Self extinguishing Halogen free

Type M, C45 & C90

Type M, C45 & C90

EN45545-2 HL3 - R22 & R23 ASTM E 162 ASTM E 662 Bombardier SMP 800-C

— EMC Screen level - EMI Screening effectiveness of EMILFH-SPL conduit

— The graph shows the results of EMILFH-SPL screened conduit, with its appropriate fittings. — The conduit is tested by ERA technology, to IEC 1196-1 Transfer Impedance. — Tests measured attenuation in decibels (dB) over the frequency range Transfer Impedance was extrapolated to per metre transfer impedance and converted to give a shielding effectiveness, demonstrated by the graph. covered by the EMC directive, 100 kHz to 1 GHz. —

— The graph shows the results of EMILFH-SPL screened conduit, with its appropriate fittings. — The conduit is testedby ERA technology, to IEC 1196-1 Transfer Impedance. — Tests measured attenuation in decibels (dB) over the frequency range covered by the EMC directive, 100 kHz to 1 GHz. — Transfer Impedance was extrapolated to per metre transfer impedance and converted to give a shielding effectiveness, demonstrated by the graph.

110

100

90

80

70

60

50

40

30

20

0.1

1

10

100

1000

Frequency (Mhz)