— Electrical switchboard

All electrical panels must comply with the safety requirements of EN 61439-1 and, where applicable, EN 61439-3.

Buildings 1

Buildings 2

In medical environments, the following types of switchboards may be required, depending on their size (reference in the figure): • general low voltage (QGBT); • main building distribution (QDPE); • floor or zone (QP)

QP

FloorsC

FloorsF

QP

Zona А

QP

QP

Zone B

Floors B

QP

— Representation of the star distribution system

QP

Floors A

FloorsD

QP

QP

The main switchboard and the distribution board of the building should be located in special rooms that are not directly communicating with the public areas and not near combustible structures or deposits of combustible material.

QDPE

QDPE

Office entrance

Cabin electric

Switchboard protection

For protection against direct contacts

Protection against external influences

IPXXD (IP4X) IPXXB (IP2X)

for horizontal surfaces at your fingertips

IPX4

in rooms where liquids are usually spilled

in rooms for which jets of water are to be used for cleaning

for all other cases

IPX5

QDPE

QGBT

Switchboard low voltage