Office Building Solution

BU I LDI NG SOLUT IONS

41

— Documents

The use and maintenance manuals for the systems and equipment must be attached, and in particular • those for the operation, testing and maintenance of accumulators and other safety sources; • a record of the visual and instrumental tests and examinations to be carried out over time; • information regarding the performance of initial and periodic visual examinations.

The documentation to be attached to the electrical installation in the medical sector consists of • single-line diagram of the ordinary distribution and safety systems block diagram for main and secondary switchboards with protection and control devices; • drawing of the building where the location of the distribution boards in the building must also be indicated; • diagram of controls; • verification of compliance with the requirements of the standard; • load list of safety services, with ordinary current and, for motors, inrush current; • functional description of safety operations and related power systems.