4/3
COMMUNI CAT ION AND CONNECT I V I T Y
For all the possible supervision modes, connec- tivity modules are necessary. Two mounting solutions are possible, one excluding the other: • Internally , it is possible to mount the Ekip Com modules in the circuit-breaker. This solution can be used on XT2, XT4 and XT5 cir- cuit-breakers. The module is mounted directly in- side the circuit-breaker with no additional space needed in the switchboard. For this configuration, dedicated internal module codes are available. • Externally, through the Ekip Cartridge. The mod- ules can be installed inside the cartridge, which is directly connected to the trip unit by a cable. Available with the XT2, XT4 and XT5 sizes. The Ekip cartridge is available in two versions de- pending on how many modules are needed.
The solution with the external cartridge permits a double or even triple communication channel, as well as redundant communication. Besides, the car- tridge solution makes it possible the use of ad- vanced functions, such as embedded ATS and more.
When an internal module is used, the Ekip Cartridge cannot be used and vice versa.
It has to be highlighted that, for the XT7 and XT7 M sizes, the modules must be installed directly on the terminal box available on the upper part of the cir- cuit-breaker. The modules are the same of the Ekip Cartridge. On the upper part of the circuit-breaker it is possible to install one Ekip Supply plus maxi- mum two additional modules.
Powered by FlippingBook