— Adaptive Protections

Benefits Thanks to the Tmax XT it is possible to have two sets of settings implemented in a single device. As a result, the following benefits are guaranteed: • Overcurrent protection and selectivity 100% guaranteed both in grid-connected and islanded conditions. • Service continuity is garanted by just adding a single unit to the switchboard in every plant con- dition. • Ease of use, thanks to the Ekip Connect software which allows an immediate and intuitive commis- sioning phase.

With the adaptive protections, when there is an utility outage, circuit-breaker A opens and B closes in order to achieve an islanded condition. In order to still guarantee selectivity, another set of protec- tion settings is required. Adding Tmax XT adaptive protections to the circuit-breaker C1 ensures this behaviour. The second protection setting is opti- mized for the characteristics of the local generator ensuring the incoming supply. Additionally, selective coordination with the load side switching devices is also guaranteed. With reference to Fig. 1: • Circuit-breaker A is open • Circuit-breaker B is closed • Circuit-breakers at position C are closed and the protection thresholds move automatically to “Set B” • Circuit-breakers at position D are closed • Circuit-breaker E is open • Molded case switch QS1 is closed • Non-priority loads can be disconnected using an- other functionality of the Tmax XT units (see next paragraph). Fig. 3 shows how it is possible to switch to a set of parameters which guarantees selective coordina- tion between circuit-breakers C and B by means of the Adaptive Protection function embedded in the trip unit of the C circuit-breakers.

10 3 s

10 3 s

B

A

10 2 s

10 2 s

10s

10s

C

C

D

D

1s

1s

10 - 1 s

10 - 1 s

10 - 2 s

10 - 2 s

10 - 3 s

10 - 3 s

10 2 kA

10 3 kA

1kA

10kA

10 2 kA

10 3 kA

1kA

10kA

Time-Current curves

Time-Current curves

— Fig. 2 - Protection thresholds during on-grid operation

— Fig. 3 - Protection thresholds during islanded operation