SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
7/22
— Signaling
AUX 250V AC/DC - Electrical specifications Power supply voltage
Operating current according to the utilization category AC-15 AC-14 AC-13 DC-14
DC-13
DC-12
4 A 5 A
5 A 6 A
6 A 6 A
- -
- -
- -
250V AC 125V AC 250V DC 110V DC
- -
- -
- -
0.03 A 0.05 A
0.03 A 0.05 A
0.3 A 0.5 A
AUX 24V DC - Electrical specifications
Power supply voltage
Operating current
5 V DC
0.001 A
30 V DC
0.1 A
400V AC auxiliary contacts 400V AC auxiliary contacts are available only for the XT2, XT4 and XT5 circuit-breakers in the following versions: • cabled (AWG17 cable section -1mm 2 ): - for fixed/plug-in circuit-breakers with 3.28ft long cables; - for withdrawable circuit-breakers with a fixed part and moving part connector. With the XT2 and XT4, the 400V auxiliary contacts take up the whole right-hand slot of the circuit-breaker. For the XT5 1Q+1SY, the 400V auxiliary contacts are available only with thermal-magnetic or Ekip Dip trip units.
— Cabled auxiliary contact
Combinations
XT2
XT4
XT5
3/4p
3/4p
3/4p
1Q 1SY 400V
F-P-W F-P-W
F-P-W F-P-W
F-P-W (1)
2Q 400V
F-P-W
F = Fixed, P = Plug-in, W = Withdrawable (1) Only for circuit-breakers with thermal-magnetic or Ekip Dip trip units.