SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
7/36
— Remote control
Installation in circuit-breakers: • 3-pole: as an alternative, the SOR or UVR can be installed in the slot on the left of the operating lever; • 4-pole: the SOR or UVR can be housed at the same time in the slot of the third and fourth pole. For with - drawable circuit-breakers, the connector for the fourth pole must be ordered to be able to install the SOR and UVR in the fourth pole. If there is a residual current release, the opening solenoid (RC SA) of the resid- ual current device must be installed in the slot of the third pole on the left of the operating lever.
SOR UVR RC SA
SOR UVR
SOR UVR
SOR Electrical specifications Version
Max power absorbed on inrush
Resistance
AC [VA]
DC [W]
Internal [ohm]
External [ohm]
12V DC
50 50 60 50 50
2.67
0 0 0 0 0 0 0
24-30V AC/DC 48-60V AC/DC
50 60 50 50 55 55
11 62
110...127V AC-110...125V DC 220...240V AC-220...250V DC
248 930
380-440V AC 480-525V AC
2300 5830
Opening time (SOR) XT1, XT2, XT3 and XT4
30ms
UVR Electrical specification Version
Power absorbed during normal operation Resistance AC [VA] DC [W] Internal [ohm]
External [ohm]
24-30V AC/DC
1.5
1.5
399
0
48V AC/DC 60V AC/DC
1 1 2
1 1 2
1447 2405 8351
100 100 390
110...127V AC-110...125V DC 220...240V AC-220...250V DC
2.5
2.5
20502 20502 20502
9000
380-440V AC 480-525V AC
3 4
39000 59000
Opening time (UVR) XT1, XT2, XT3 and XT4
30ms