SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
7/44
— Remote control
The direct action motor operator available for XT1 and XT3 is supplied: • with 3.28 ft long cables; • with a flange, to replace the standard one supplied with the circuit-breaker; • with a padlock device, only removable when the motor is in the open position. The padlock device ac- cepts up to three 0.3 in padlocks; • auxiliary contacts (AU-MO), which allow the motor control mode (manual or auto) signal to be routed outside; • (on request) the motor operator can be fitted with a key lock (see the Chapter "Accessories" - section "Locks"). Operating principles: • a selector on the front of the MOD, is used for selecting the operating mode: - AUTO: when the selector is in this position, the circuit-breaker closing is commanded remotely only by means of an electric impulse, whereas opening is allowed both remotely and from the front of the motor; - MANUAL: when the selector is in this position, the circuit-breaker can only be opened/closed from the front of the motor by means of the relative lever housed in a slot made in the motor itself; • via remote control, guaranteed by permanent electrical opening/closing impulses.
Operating mode: Manual
Operating mode: Auto
I: ON
I: ON
Close
Close
SOR / UVR / SA release tripping / TU
SOR / UVR / SA release tripping / TU
OFF push- button from remote
Move the lever to Reset
Move the lever to Close
ON push- button from remote
O: OFF
O: OFF
Close
Close
OFF push - button from remote
Move the lever to Reset
O: OFF
O: OFF
Reset
Reset
Stored energy motor operators - MOE and MOE-E XT2-XT4
Lever to recharge the springs
Signaling of the springs status: charged springs/ discharged springs
Optional transparent lock of the AUTO-MANUAL selector (always supplied)
AUTO-MANUAL-LOCKED selector
Signaling of the circuit-breaker status ON-OFF
— Stored energy motor operators (MOE)
Slot for padlock device
Closing push-button
Opening push-button