SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
7/68
— Residual current protection
Power supply Voltage
/A AC [V] /P AC [V] /P DC [V]
115-230...415
110...690 110...125
Operating frequency
[Hz]
45÷66
Inrush current
/A /A /A /P /P /P /A /P /P /P /P
@115 V AC @230 V AC @415 V AC @110 V AC @690 V AC @125 V DC @115 V AC @230 V AC @690 V AC @125 V DC
500 mA for 50 ms 150 mA for 50 ms 100 mA for 50 ms 300 mA for 50 ms
2 A for 50 ms
500 mA for 50 ms
Rated Power
2 [VA] / 2 [W]
max 3 W max 3 W max 4 W max 2 W
Trip threshold adjustment IΔn
[A] [s]
0.03-0.05-0.1-0.3-0.5-1-3-5-10-30
No trip time adjustment
instantaneous 0.1-0.2-0.3-0.5-0.7-1-2-3-5
Pre-alarm threshold
x IΔn
25%
A type for pulsing alternate current Signals Device powered visual signaling
Visual signaling of device not functioning / not configured
Visual signaling of residual current protection
Electrical alarm/pre-alarm signal
Electric trip signal
Controls Remotely controlled opening command Remotely controlled reset command Operating range of closed transformers Ø 2.36 [in] toroidal transformer Ø 4.33 [in] toroidal transformer Ø 7.28 [in] toroidal transformer Connection to toroidal transformer
[A] [A] [A]
In max = 250 A - Use 0.03...30 A In max = 400 A - Use 0.03...30 A In max = 800 A - Use 0.1...30 A
By means of 4 shielded or twisted conductors. Maximum tolerated length: 50 ft
Dimensions W x H x D
[mm/in] [mm/in]
[96x96x77] / [3.77x3.77x3]
Drilling for assembly on door
[92x92] / [6.62x3.62] IEC 60947-2 annex M
standard