Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

7/68

— Residual current protection

Power supply Voltage

/A AC [V] /P AC [V] /P DC [V]

115-230...415

110...690 110...125

Operating frequency

[Hz]

45÷66

Inrush current

/A /A /A /P /P /P /A /P /P /P /P

@115 V AC @230 V AC @415 V AC @110 V AC @690 V AC @125 V DC @115 V AC @230 V AC @690 V AC @125 V DC

500 mA for 50 ms 150 mA for 50 ms 100 mA for 50 ms 300 mA for 50 ms

2 A for 50 ms

500 mA for 50 ms

Rated Power

2 [VA] / 2 [W]

max 3 W max 3 W max 4 W max 2 W

Trip threshold adjustment IΔn

[A] [s]

0.03-0.05-0.1-0.3-0.5-1-3-5-10-30

No trip time adjustment

instantaneous 0.1-0.2-0.3-0.5-0.7-1-2-3-5

Pre-alarm threshold

x IΔn

25%

A type for pulsing alternate current Signals Device powered visual signaling

Visual signaling of device not functioning / not configured

Visual signaling of residual current protection

Electrical alarm/pre-alarm signal

Electric trip signal

Controls Remotely controlled opening command Remotely controlled reset command Operating range of closed transformers Ø 2.36 [in] toroidal transformer Ø 4.33 [in] toroidal transformer Ø 7.28 [in] toroidal transformer Connection to toroidal transformer

[A] [A] [A]

In max = 250 A - Use 0.03...30 A In max = 400 A - Use 0.03...30 A In max = 800 A - Use 0.1...30 A

By means of 4 shielded or twisted conductors. Maximum tolerated length: 50 ft

Dimensions W x H x D

[mm/in] [mm/in]

[96x96x77] / [3.77x3.77x3]

Drilling for assembly on door

[92x92] / [6.62x3.62] IEC 60947-2 annex M

standard