— Thermal-magnetic trip unit Settings

Available settings for TMF and TMA trip units: Circuit Breaker Trip Unit In [A]

L - Overload

I - Short Circuit

I1 [A] MIN.

I3 [A] MIN.

MED.

MAX.

MED.

MAX.

XT1

TMF

15 20 25 30 35 40 45 50 60 70 80 90

15 20 25 30 35 40 45 50 60 70 80 90

500 500 500 500 500 500 500 500 600 700 800 900

100 110 125

100 110 125

1000 1100 1250 400

XT2

TMF

15 20 25 30 35 40 50 60 70 80 90

15 20 25 30 35 40 50 60 70 80 90

400 400 400 400 400 500 600 700 800 900

TMA

56 63 70 77 88

68 77 85 94

400 450 500 550 625

600 675 750 825 937

100 110 125

100 110 125

1000 1100 1250 600

107

XT3

TMF

60 70 80 90

60 70 80 90

700 800 900

100 110 125 150 175 200 225

100 110 125 150 175 200 225

1000 1100 1250 1500 1750 2000 2250 400

XT4

TMF

25 30 35 40 50 60 70 80 90

25 30 35 40 50 60 70 80 90

400 400 400 500 600 700 800 900

100 110 125 150 175 200 225 250 100 110 125 150 175 200 225 250 80 90 300 400 500 600 600 800

100 110 125 150 175 200 225 250 100 110 125 150 175 200 225 250 80 90 300 400 500 600 600 800

1000 1100 1250 1500 1750 2000 2250 2500 1000 1100 1250 1500 1750 2000 2250 2500 800 900 3000 4000 5000 6000 6000 8000

TMA

56 63 70 77 88

68 77 85 94

400 450 500 550 625 750 875

600 675 750 825

106 128 149 170 192 213 255 340 425 510 510 680

938 1125 1313 1500 1688 1875 2250 3000 3750 4500 4500 6000

105 123 140 158 175 210 280 350 420 420 560

1000 1125 1250 1500 2000 2500 3000 3000 4000

XT5

TMA

XT6

TMA