Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

3/24

— Ekip Dip Protection settings

Available settings for Ekip Dip trip units:

Ekip DIP LS/I & Ekip DIP LIG ABB code Protection Function Threshold

Trip Time

Trip Curve

L

Overload

I1 = 0.4...1 x In with steps of 0.04

t1 at 3 x I1 = 12 - 36s 12 - 48s for XT7 t2 = 0.1 - 0.2s at 10 x In when t = k/I2

t=k/I 2

S

Selective short-circuit I2 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 – 6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In

t=k t = k or t = k/I 2 for XT7

I

Short-circuit

I3 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 – 6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In I4 = Off - 0.20 - 0 .25 - 0.45 - 0.55 - 0.75 - 0.80 – 1 x In I4 = Off - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 0.9 - 1.0 x In for XT7

t3 ≤ 20ms t3 ≤ 30ms for XT7

t=k

G

Earth fault

t4 = 0.1 - 0.2 - 0.4 - 0.8s at 3 x In when t = k/I2

t=k t = k or t = k/I 2 for XT7

Ekip DIP LSI & Ekip DIP LSIG ABB code Protection Function Threshold

Trip Time

Trip Curve

L

Overload

I1 = 0.4...1 x In with steps of 0.02 I1 = 0.4 - 0.42 - 0.45 - 0.47 - 0.5 - 0.52 - 0.55 - 0.57 - 0.6 - 0.62 - 0.65 - 0.67 - 0.7 - 0.72 - 0.75 - 0.77 - 0.8 - 0.82 - 0.85 - 0.87 - 0.9 - 0.92 - 0.95 - 0.97 - 1 x In for XT7

t1 at 3xI1 = 3 - 12 - 36 - 60s at 3xI1 for XT2-XT4

t=k/I 2

3 - 12 - 36 - 48s for XT5 3 - 12 - 36 - 72 for XT6 3 - 12 - 24 - 36 - 48 - 72 - 108 - 144s for XT7 t2 = 0.05 - 0.1 - 0.2 - 0.4 for XT2-XT4-XT5-XT6 t2 = 0.1 - 0.2 - 0.3 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 for XT7 at 10xIn when t = k/I 2

S

Selective short-circuit I2 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 – 6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In I2 = Off – 0.6 - 0.8 - 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4 - 5 - 6 – 7 – 8 – 9 – 10 for XT7

t = k or t = k/I 2

I

Short-circuit

I3 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 – 6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In I3 = Off – 1 .5 – 2 – 3 – 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 -13 - 14 - 15 for XT7 I4 = Off - 0.20 - 0 .25 - 0.45 - 0.55 - 0.75 - 0.80 – 1 x In I4 = Off 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 0.9 - 1.0 x In for XT7

t3 ≤ 40ms t3 ≤ 30ms for XT7

t=k

G

Earth fault

t4 = 0.1 - 0.2 - 0.4 - 0.8s at 3 x In when t = k/I2

t=k t = k or t = k/I 2 for XT7

Ekip M DIP I ABB code Protection Function Threshold

Trip Time

Trip Curve

I

Short-circuit

I3 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 – 6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In

t3 ≤ 15ms for XT2-XT4 t3 ≤ 20ms for XT5-XT6 t3 ≤ 30ms for XT7

t=k

Ekip M DIP LIU ABB code Protection Function Threshold

Trip Time

Trip Curve

L

Overload

I1 = 0.4...1 x In with steps of 0.04

Operating Class for XT2-XT4: 5E - 10E - 20E Operating Class for XT5-XT6: 5E - 10E - 20E - 30E

t=k/I 2

I

Short-circuit

I3 = 6 – 7 – 8 – 9 - 10 – 11 – 12 - 13 x In

t3 ≤ 15ms for XT5-XT4 t3 ≤ 20ms for XT5-XT4 t3 ≤ 30ms for XT7

t=k

U

Phase loss (IEC 60947-4-1)

ON/OFF

When ON t6 = 2s

t=k