Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

3/26

— Ekip Dip Protection settings

Tolerances in other conditions: Trip Unit Protection

Trip Threshold

Trip Time

Ekip DIP LS/I Ekip DIP LIG Ekip G Dip LS/I

L S

trip between 1.05…1.3 x I1 according IEC 60947-2 ±20%

±10% ±15%

±20%

I

≤60ms

G

± 30% For In=10A Ifault min=4A For In=25A Ifault min=9A

± 20% For In=10A,25A: ±30%

Ekip DIP LSI Ekip DIP LSIG

L S

trip between 1.05…1.3 x I1 according IEC 60947-2 ±20%

±10% ±15%

±20%

I

≤60ms

G

XT2-XT4-XT5-XT6 ± 30%

XT2-XT4-XT5-XT6 ± 20% For In=10A,25A: ±30% XT7 t=k the better of the two data: ±10% or ±40ms t=k/I2: ± 15%

For In=10A Ifault min=4A For In=25A Ifault min=9A XT7 ± 7% trip between 1.05…1.2xI1

Ekip M Dip I Ekip M Dip LIU

L

±20%

I

±15% ±20%

≤60ms

U

±20%

Powered by