Tmax XT UL Catalog - Ed. 2021

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

3/34

— Ekip Touch/Hi-Touch Protection functions

ABB Code

ANSI Code

Function

Ekip Touch LSI

Ekip Touch LSIG

Ekip Touch Measuring LSI

Frequency Protection package UF 81L

Underfrequency Overfrequency

OF

81H

UF2 OF2

81L

2nd Underfrequency 2nd Overfrequency

81H

Power Protection package RP 32R

Reverse active power

Cos ϕ

78 67

Power Factor

D

Directional overcurrent Loss of field or reverse reactive power Reactive overpower

RQ

40/32R

OQ OP UP

320F 320F 32LF

Active overpower Active underpower

ROCOF Protection package ROCOF 81R

Rate of change of frequency

Adaptive Protection package Set A-B

Dual Setting

Motor Protection L

Motor protection overload Rotor bloackage Phase lack and/or unbalance

R U

51LR

46

Uc

37

Undercurrent

Protection with additional modules SC 25

Synchrocheck

●

●

●

Ekip CI

Motor contactor interface protection PTC for temperature

PTC

G ext

50G TD/86/51G 64 50N TD 87N

Earth fault

● (1)

Rc

Residual current / Differential ground fault

● (1)

● Available

Available with the corresponding software package

(1) Available with additional module for XT7 and XT7 M only

When an Ekip Touch LSI or LSIG trip unit is upgraded with one of the following packages: • Voltage Protection • Voltage Protection Advanced • Frequency Protection • Power Protection • ROCOF Protection it is mandatory to add first the Measuring package described on the following pages.

Powered by