SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
3/34
— Ekip Touch/Hi-Touch Protection functions
ABB Code
ANSI Code
Function
Ekip Touch LSI
Ekip Touch LSIG
Ekip Touch Measuring LSI
Frequency Protection package UF 81L
Underfrequency Overfrequency
OF
81H
UF2 OF2
81L
2nd Underfrequency 2nd Overfrequency
81H
Power Protection package RP 32R
Reverse active power
Cos ϕ
78 67
Power Factor
D
Directional overcurrent Loss of field or reverse reactive power Reactive overpower
RQ
40/32R
OQ OP UP
320F 320F 32LF
Active overpower Active underpower
ROCOF Protection package ROCOF 81R
Rate of change of frequency
Adaptive Protection package Set A-B
Dual Setting
Motor Protection L
Motor protection overload Rotor bloackage Phase lack and/or unbalance
R U
51LR
46
Uc
37
Undercurrent
Protection with additional modules SC 25
Synchrocheck
●
●
●
Ekip CI
Motor contactor interface protection PTC for temperature
PTC
G ext
50G TD/86/51G 64 50N TD 87N
Earth fault
● (1)
Rc
Residual current / Differential ground fault
● (1)
● Available
Available with the corresponding software package
(1) Available with additional module for XT7 and XT7 M only
When an Ekip Touch LSI or LSIG trip unit is upgraded with one of the following packages: • Voltage Protection • Voltage Protection Advanced • Frequency Protection • Power Protection • ROCOF Protection it is mandatory to add first the Measuring package described on the following pages.
Powered by FlippingBook