Tmax XT UL Catalog - Ed. 2021

UV

t8

V I

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

3/40

t t

t — Ekip Touch/Hi-Touch Protection functions V V U9 t8 9 OV U U8 t8 t

f12

UF OV

U9

t12

t8 9

f V

OF Overfrequency (ANSI 81H) With a constant trip time (t = k), this trips when network frequency exceeds a set threshold.

t

t

OF UF

f13

f12

t13

t12 t12

nverse e

f

f

nverse

voltage unbalance UF2 & OF2 Second protection against underfrequency and overfrequency (ANSI 81L and 87H) This enables two minimum and maximum frequency thresholds to be set simultaneously. For example, just an alarm can be set for tripping when the first threshold is reached, and the circuit-breaker can be set to be opened when the second threshold is reached. OF

t

t

PE

L1 L2 L3 N

f17

mean

f12 t17 f13

U14

t12

t13

f f

U1 U2 U3 LOAD

RP Reverse active power With a constant trip time (t = k), this trips when the total active power – in the opposite direction of the current exceeds the set threshold.

V1

mean

senso ciclico voltage unbalance

U14

V3

V2

RP

U1 U2 U3

Cos ϕ Power factor Available with a three-phase threshold, this provides a warning when the system operates with a power factor that is lower than the set power factor.

V1

senso ciclico

V3

V2

D Directional overcurrent This form of protection is able to recognize the direction of the current during the fault period and thus detect if the fault is upstream or downstream of the circuit-breaker. The protection, with a fixed time trip curve (t=k), intervenes with two different time delays (t7bw and t7fw), according to the current direction. In ring distribution networks, it enables the identification and disconnection of the area in which a fault has occurred, while maintaining operation in the rest of the installation. Zone selectivity for protection D This enables the possibility to interconnect more circuit-breakers, so that, in case of a fault, the affected area can be disconnected nearest to the fault and operation in the rest of the installation is maintained. It is possible to enable directional zone selectivity alternatively to zone selectivity of S and G protections. This also works in the presence of an auxiliary supply. Start-up function for protection D This enables higher trip thresholds to be set at the outgoing point, as available for protections S, I and G.

Generator

LOAD B

LOAD A

Forward power flow

FAULT