— Ekip Touch/Hi-Touch Protection settings

Available settings for each protection function:

ABB Code

ANSI Code

Function

Threshold Range

Threshold Step

Protections L

49

Overload according to 60947-2

I1 = 0.4…1 x In

0.001 x In

49

Overload according to 60255-151

I1 = 0.4…1 x In

0.001 x In

S

50 TD

Time-delayed overcurrent

I2 = 0.6…10 x In

0.1 x In

68

Zone selectivity Start up

Activation: 0.6…10 x In

0.1 x In 0.1 x In

51

Time-delayed overcurrent

I2 = 0.6…10 x In

I

50

Instantaneous short-circuit

XT2-XT4-XT5: I3 = 1.5…10 x In XT7: I3 = 1.5…15 x In Activation: XT2-XT4-XT5: I3 = 1.5…10 x In XT7: I3 = 1.5…15 x In

0.1 x In

Start up

0.1 x In

G (1)

50N TD

Earth fault

I4 = 0.1…1 x In

0.001 x In

68

Zone selectivity Start up

Activation: 0.2…10 x In

0.02 x In 0.001 x In

51N

Earth fault

I4 = 0.1…1 x In

N

Neutral

On/Off

50%-100%-200% of the phases

2I

50

Programmable 2nd Instantaneous short-circuit

XT2-XT4-XT5: I3 = 1.5…10 x In XT7: I3 = 1.5…15 x In XT2-XT4-XT5: I3 = 1.5…10 x In XT7: I3 = 1.5…15 x In I6 = 2…90% In unbalance

0.1 x In

MCR

Closing on short-circuit

0.1 x In

IU

46

Current unbalance Current threshold Activation up/down

1% In

LC1/2 Iw1/2

-

LC1 = 50…100% x I1 LC2 = 50…100% x I1 Iw1 = 0.1…10 x In Iw1 = 0.1…10 x In

1% 1%

0.01 x In

S2

50 TD

2nd Time-delayed overcurrent

I2 = 0.6…10 x In

0.1 x In

68

Zone selectivity Start up

Activation: 0.6…10 x In

0.1 x In

Phase Sequence

47 27 59 27 59

Cyclical direction of the phases

1-2-3 or 3-2-1

UV OV

Undervoltage Overvoltage

U8 = 0.5….0.98 x Un U9 = 1.02….1.5 x Un U15 = 0.5….0.98 x Un U16 = 1.02….1.5 x Un

0.001 x Un 0.001 x Un 0.001 x Un 0.001 x Un

UV2 OV2

2nd Undervoltage 2nd Overvoltage