Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

3/50

— Ekip Touch/Hi-Touch Protection settings

ABB Code

ANSI Code

Function

Threshold Range

Threshold Step

Protections VU

47

Voltage unbalance

U14 = 2…90 % Un unbalance

1% Un 0.1 x In

S(V)

51V

Voltage controlled overcurrent Step mode (controlled mode)

I20 = 0.6...10 x In Ul = 0.2…1 x Un

0.01 x Un

Ks = 0.1…1

0.01

51V

Linear mode (restrained mode)

Ul = 0.2…1 x Un Uh = 0.2…1 x Un

0.01 x Un 0.01 x Un

Ks = 0.1…1

0.01

S2(V)

51V

2nd Voltage controlled overcurrent

I21 = 0.6...10 x In Ul2 = 0.2…1 x Un

0.1 x In

Step mode (controlled mode)

0.01 x Un

Ks2 = 0.1…1

0.01

51V

Linear mode (restrained mode)

Ul2 = 0.2…1 x Un Uh2 = 0.2…1 x Un

0.01 x Un 0.01 x Un

Ks2 = 0.1…1

0.01

RV UF OF

59N 81L 81H 81L 81H 32R

Residual overvoltage

U22 = 0.05….0.5 x Un f12 = 0.9….0.999 fn f13 = 1.001….1.1 fn f17 = 0.9….0.999 fn f18 = 1.001….1.1 fn P11 = -1…-0.05 Sn Cos φ = 0.5…0.95 I7 Fw/Bw = 0.6...10 x In

0.001 x Un 0.001 x fn 0.001 x fn 0.001 x fn 0.001 x fn 0.001 Sn

Underfrequency Overfrequency

UF2 OF2

2nd Underfrequency 2nd Overfrequency Reverse active power

RP

Cos ϕ

78 67 68

Power factor

0.01

D

Directional overcurrent

0.1 x In

Zone selectivity Start up

Activation: 0.6…10 x In

0.1 x In

Minimum angle of direction (°)

3.6, 7.2, 10.8, 14.5, 18.2, 22, 25.9, 30, 34.2, 38.7, 43.4, 48.6, 54.3, 61, 69.6

RQ

40/32R

Loss of field or reverse reactive power

Q24 = -1…-0.1 x Sn

0.001 x Sn

Kq = -2…2

0.01

Loss of field or reverse reactive power

Q25 = -1…-0.1 x Sn

0.001 x Sn

Kq = -2…2

0.01 0.01

Minimum voltage threshold

Vmin. = 0.5…1.2 Q27 = 0.4…2 x Sn P26 = 0.4…2 x Sn P23 = 0.1...1 x Sn

OQ OP UP

320F 320F 32LF

Reactive overpower Active overpower Active underpower

0.001 x Sn 0.001 x Sn 0.001 x Sn

StartUp

ROCOF

81R

Rate of change of frequency Motor protection overload

f28 = 0.4…10 Hz / s (up &/or down) 0.2 Hz/s

L (Motor Protection)

49

I1 = 0.4…1 x In

0.001 x In

According 60947-4-1 Rotor blockage - Jam Rotor blockage - Stall

R

51R 51R

Ij = 2…10 x I1 Is = 1…10 x I1

0.1 0.1

U

Phase lackand/or unbalance

On/Off

-

Uc

37

Undercurrent

50…90% x I1

10%

Powered by