SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
3/52
— Ekip Touch/Hi-Touch Protection settings
ABB Code
ANSI Code
Function
Threshold Range
Threshold Step
Protection with additional modules SC Synchrocheck 25
Synchrocheck (Live busbars)
Ulive = 0.5…1.1 x Un ΔU = 0.02…0.12 x Un Δf = 0.1…1 x Hz Δ� 5…50° elt Ulive = 0.5…1.1 x Un Udead = 0.02…0.2 x Un
0.001 x Un 0.001 x Un 0.1 x Hz 5° elt 0.001 x Un 0.001 x Un
Synchrocheck (Live/Dead busbars) Frequency check off Phase check off Dead bar configuration
Reverse/Standard
Primary voltage
100…1150
100, 115, 120, 190, 208, 220, 230, 240, 277, 347, 380, 400, 415, 440, 480, 500, 550, 600, 660, 690, 910, 950, 1000, 1150
Secondary voltage
100…120
100, 110, 115, 120
Gext
I41 (1) = 0.1…1 x In toroid
0.001 x In toroid
50G TD
Earth fault
68
Zone selectivity Start up
Activation: 0.1…1 x In
0.02 x In
51G
Earth fault Earth fault
I41 (1) = 0.1…1 x In
0.001 x In
MDGF (2)
I41 = 0.1…1 x In toroid Max setting 1200A
0.001 x In toroid
Earth fault
I41 = 0.1…1 x In
0.001 x In
Rc
64 50N TD 87N Residual current / Differential ground fault IΔn = 3 - 5 - 7 - 10 – 20 – 30A
The RC for the XT7 is active only when the rating plug is present. All of the Synchrocheck functions are for signaling. An adjustable pre-alarm threshold (50...90%) is available for L protection, as well as a fixed pre-alarm threshold is available for G and Gext protection. (1) With Vaux all thresholds are available. Without Vaux there are minimum threshold limitations. Details available on the "User manual for use and maintenance of Ekip Touch Trip units" (2) Available for XT7 only.