SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

3/52

— Ekip Touch/Hi-Touch Protection settings

ABB Code

ANSI Code

Function

Threshold Range

Threshold Step

Protection with additional modules SC Synchrocheck 25

Synchrocheck (Live busbars)

Ulive = 0.5…1.1 x Un ΔU = 0.02…0.12 x Un Δf = 0.1…1 x Hz Δ� 5…50° elt Ulive = 0.5…1.1 x Un Udead = 0.02…0.2 x Un

0.001 x Un 0.001 x Un 0.1 x Hz 5° elt 0.001 x Un 0.001 x Un

Synchrocheck (Live/Dead busbars) Frequency check off Phase check off Dead bar configuration

Reverse/Standard

Primary voltage

100…1150

100, 115, 120, 190, 208, 220, 230, 240, 277, 347, 380, 400, 415, 440, 480, 500, 550, 600, 660, 690, 910, 950, 1000, 1150

Secondary voltage

100…120

100, 110, 115, 120

Gext

I41 (1) = 0.1…1 x In toroid

0.001 x In toroid

50G TD

Earth fault

68

Zone selectivity Start up

Activation: 0.1…1 x In

0.02 x In

51G

Earth fault Earth fault

I41 (1) = 0.1…1 x In

0.001 x In

MDGF (2)

I41 = 0.1…1 x In toroid Max setting 1200A

0.001 x In toroid

Earth fault

I41 = 0.1…1 x In

0.001 x In

Rc

64 50N TD 87N Residual current / Differential ground fault IΔn = 3 - 5 - 7 - 10 – 20 – 30A

The RC for the XT7 is active only when the rating plug is present. All of the Synchrocheck functions are for signaling. An adjustable pre-alarm threshold (50...90%) is available for L protection, as well as a fixed pre-alarm threshold is available for G and Gext protection. (1) With Vaux all thresholds are available. Without Vaux there are minimum threshold limitations. Details available on the "User manual for use and maintenance of Ekip Touch Trip units" (2) Available for XT7 only.