Tmax XT UL Catalogo [EN]

PROTECT ION TR I P UNI TS

3/55

ABB Code ANSI Code Function

Threshold Range

Trip Time

RP

32R

Reverse active power

± 10%

The better of the two data: ± 10% or ± 40ms (for t11<5s) / ± 100ms (for t11 ≥ 5s)

D

68

Directional overcurrent

± 7% I ≤ 6 x In ± 10% I ≥ 6 x In

If t7 ≤ 200 ms : +/-20 ms If 200ms < t7 ≤ 400 ms : 10% If con t7 > 400 ms : 40 ms

RQ

40/32R

Loss of field or reverse reactive power ± 10%

The better of the two data: ± 10% or ± 40ms (for t24<5s) / ± 100ms (for t24 ≥ 5s) The better of the two data: ± 10% or ± 40ms (for t27<5s) / ± 100ms (for t27 ≥ 5s) The better of the two data: ± 10% or ± 40ms (for t26<5s) / ± 100ms (for t26 ≥ 5s) The better of the two data: ± 10% or ± 40ms (for t23<5s) / ± 100ms (for t23 ≥ 5s)

OQ

320F

Reactive overpower

± 10%

OP

320F

Active overpower

± 10%

UP

32LF

Active underpower

± 10%

ROCOF

81R

Rate of change of frequency

± 10% (20% when "0,4Hz/s" is set)

The better of the two data: ± 20% or ± 200ms

L (Motor Protection)

Motor protection overload According 60947-4-1

R

51LR 51LR

Rotor blockage - Jam Rotor blockage - Stall

Ij = 2…10 x I1 Is = 1…10 x I1

tj = 1…10 s ts = 2…10 s

U

Phase lack and/or unbalance

± 10%

The better of the two data: ± 10% or ± 40ms (for tu<5s) / ± 40ms (for tu≥5s) The better of the two data: ± 10% or ± 40ms (for tuc<5s) / ± 40ms (for tuc≥5s)

Uc

37

Undercurrent

± 10%

Protection with additional modules SC Synchrocheck 25

Synchrocheck (Live busbars)

10% 10% ± 7%

Synchrocheck (Live. Dead busbars)

Gext

50GTD

Earth fault

The better of the two data: ± 10% or ± 40ms

51G 51G

Earth fault Earth fault Earth fault

± 7%

± 15%

± 7%

The highest between 15% or 15ms

MDGF (2)

Rc

64 50N TD 87N

Residual current / Differential ground fault

- 20% ÷ 0%

140ms @max trip time 950ms @max trip time

(1) 2I Trip time with Vaux only: - ≤ 3ms when the fault current is above 18kA - ≤ 7ms (three-phase) or ≤9ms (single-phase) when the fault is greater than three times the 2I setting (I31) - ≤ 15ms when the fault is lower than three times the 2I setting (I31) (2) Available for XT7 only

The tolerances above apply to trip units already powered by the main circuit with current flowing in at least two phases or an auxiliary power supply. In all other cases the following tollerance values apply:

ABB Code

Trip threshold

Trip time

L S

Trip between 1.05 and 1.2 x I1 ± 20%

± 10% ± 15% ± 10% ± 15%

± 20% ≤ 60ms

I

G

± 20% (60ms when t4=inst)

Other protection

± 20%

Powered by