PROTECT ION TR I P UNI TS
3/55
ABB Code ANSI Code Function
Threshold Range
Trip Time
RP
32R
Reverse active power
± 10%
The better of the two data: ± 10% or ± 40ms (for t11<5s) / ± 100ms (for t11 ≥ 5s)
D
68
Directional overcurrent
± 7% I ≤ 6 x In ± 10% I ≥ 6 x In
If t7 ≤ 200 ms : +/-20 ms If 200ms < t7 ≤ 400 ms : 10% If con t7 > 400 ms : 40 ms
RQ
40/32R
Loss of field or reverse reactive power ± 10%
The better of the two data: ± 10% or ± 40ms (for t24<5s) / ± 100ms (for t24 ≥ 5s) The better of the two data: ± 10% or ± 40ms (for t27<5s) / ± 100ms (for t27 ≥ 5s) The better of the two data: ± 10% or ± 40ms (for t26<5s) / ± 100ms (for t26 ≥ 5s) The better of the two data: ± 10% or ± 40ms (for t23<5s) / ± 100ms (for t23 ≥ 5s)
OQ
320F
Reactive overpower
± 10%
OP
320F
Active overpower
± 10%
UP
32LF
Active underpower
± 10%
ROCOF
81R
Rate of change of frequency
± 10% (20% when "0,4Hz/s" is set)
The better of the two data: ± 20% or ± 200ms
L (Motor Protection)
Motor protection overload According 60947-4-1
R
51LR 51LR
Rotor blockage - Jam Rotor blockage - Stall
Ij = 2…10 x I1 Is = 1…10 x I1
tj = 1…10 s ts = 2…10 s
U
Phase lack and/or unbalance
± 10%
The better of the two data: ± 10% or ± 40ms (for tu<5s) / ± 40ms (for tu≥5s) The better of the two data: ± 10% or ± 40ms (for tuc<5s) / ± 40ms (for tuc≥5s)
Uc
37
Undercurrent
± 10%
Protection with additional modules SC Synchrocheck 25
Synchrocheck (Live busbars)
10% 10% ± 7%
Synchrocheck (Live. Dead busbars)
Gext
50GTD
Earth fault
The better of the two data: ± 10% or ± 40ms
51G 51G
Earth fault Earth fault Earth fault
± 7%
± 15%
± 7%
The highest between 15% or 15ms
MDGF (2)
Rc
64 50N TD 87N
Residual current / Differential ground fault
- 20% ÷ 0%
140ms @max trip time 950ms @max trip time
(1) 2I Trip time with Vaux only: - ≤ 3ms when the fault current is above 18kA - ≤ 7ms (three-phase) or ≤9ms (single-phase) when the fault is greater than three times the 2I setting (I31) - ≤ 15ms when the fault is lower than three times the 2I setting (I31) (2) Available for XT7 only
The tolerances above apply to trip units already powered by the main circuit with current flowing in at least two phases or an auxiliary power supply. In all other cases the following tollerance values apply:
ABB Code
Trip threshold
Trip time
L S
Trip between 1.05 and 1.2 x I1 ± 20%
± 10% ± 15% ± 10% ± 15%
± 20% ≤ 60ms
I
G
± 20% (60ms when t4=inst)
Other protection
± 20%