VD4 - INTERRUTTORI DI MEDIA TENSIONE IN VUOTO 12...40,5 kV - 630...4000 A - 16...63 kA
46
— Scelta e ordinazione Interruttori estraibili
Interruttore estraibile VD4 (24 kV) per quadro UniGear ZS1
Ur
Isc
Corrente termica nominale (40 °C) [A]
L=800
L=1000
L=1000
L=1000
Tipo interruttore
I=210
I=275
I=275
I=275
kV
kA
u/l=310
u/l=310
u/l=310
u/l=310
ø=35
ø=35
ø=79
ø=109
16 20 25 16 20 25
630 630 630
VD4/P 24.06.16 p210 VD4/P 24.06.20 p210 VD4/P 24.06.25 p210 VD4/P 24.12.16 p210 VD4/P 24.12.20 p210 VD4/P 24.12.25 p210 VD4/P 24.12.32 p210 VD4/P 24.06.16 p275 VD4/P 24.06.20 p275 VD4/P 24.06.25 p275 VD4/P 24.12.16 p275 VD4/P 24.12.20 p275 VD4/P 24.12.25 p275 VD4/P 24.12.32 p275 VD4/P 24.16.16 p275 VD4/P 24.16.20 p275 VD4/P 24.16.25 p275 VD4/P 24.16.32 p275 VD4/P 24.20.16 p275 VD4/P 24.20.20 p275 VD4/P 24.20.25 p275 VD4/P 24.20.32 p275 VD4/P 24.25.16 p275 VD4/P 24.25.20 p275 VD4/P 24.25.25 p275 VD4/P 24.25.32 p275 VD4/P 24.32.32 p275
1250 1250 1250 1250
31,5
16 20 25 16 20 25
630 630 630
1250 1250 1250 1250
24
31,5
16 20 25
1600 1600 1600 1600 2000 2000 2000 2000
31,5
16 20 25
31,5
2300 ( 1 ) 2300 ( 1 ) 2300 ( 1 ) 2300 ( 1 )
16 20 25
31,5 31,5
2700 ( 2 )
L = larghezza del quadro. I = interasse orizzontale dei poli. u/l = distanza tra terminale superiore e inferiore. ø = diametro dei contatti di sezionamento.
( 1 ) 2500 A corrente nominale garantita con ventilazione forzata. ( 2 ) 3150 A corrente nominale garantita con ventilazione forzata.