Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

7/24

— Signaling

AUX for XT7 and XT7 M Circuit -breakers XT7

XT7 M

AUX

Q

SY

S51

S52

Q

S51

RTC

24V DC

250V AC/DC

 (1)

 (1)

 (1)

400V AC

-

-

-

-

(1) Same commercial code of AUX 400V

Open / closed auxiliary contacts - Q The XT7 and XT7 M circuit-breakers can be equipped with auxiliary contacts that signal the open or closed status of the circuit-breaker. The contacts are available in the following configurations:

Open / closed auxiliary contacts (AUX 4Q)

XT7

XT7 M

— Open and close auxiliary contacts

4 auxiliary contacts

4Q 400V AC/DC

4Q 24V DC

2Q 400V AC/DC + 2Q 24V DC

15 auxiliary contacts

15Q 400V AC/DC

15Q 24V DC

400V/250V AC/DC contact

24V DC contact

Type

Changeover contacts

Changeover contacts

Minimum load

100mA @ 24V

1mA @ 5V

Breaking capacity DC

— 15 auxiliary contacts

24V

-

0.1A

125V 250V 250V

0.3A @ 10ms 0.15A @ 10ms 5A @ cos ϕ 1 5A @ cos ϕ 0.7 5A @ cos ϕ 0.3 3A @ cos ϕ 1 2A @ cos ϕ 0.7 1A @ cos ϕ 0.3

- - - - - - - -

AC

400V

The AUX 15Q is an alternative to the mechanical interlock (MI), the DLC for XT7 M lock or the DLP lock if mounted on the right side.