Tmax XT UL Catalogo [EN]

7/25

ACCESSOR I ES

Trip auxiliary contact - SY The XT7 circuit-breakers can be equipped with auxiliary contacts that signal that the circuit-breaker is opening due to the intervention of the trip unit, or to the opening of undervoltage/shunt opening releases, or to the use of the test button. The contacts are available in the following configurations:

400V/250V AC/DC contact

24V DC contact

Type

Switching

Switching 1mA @ 5V

Minimum load

100mA @ 24V

Breaking capacity DC

24V

-

0.1A

125V 250V 250V 400V

0.3A

- - - -

0.15A

AC

12A

3A

Contact signaling the tripping of the protection unit Ekip – S51 This contact signals the opening of the circuit-breaker after the Ekip protection trip unit has tripped. The contact is available for the XT7 and XT7 M. For the XT7 M circuit-breaker, the closing operation can be carried out only after the “TU Reset” push-button has been restored to its normal operating position. The switching contact can also be associated with an optional accessory for remote resetting - YR.

250V AC/DC contact

24V DC contact

Type

Switching

Switching 1mA @ 5V

Minimum load

100mA @ 24V

— Contact signaling the tripping of the Ekip trip unit protection - S51

Breaking capacity DC

24V

-

0.1A

250V 250V

0.5A @ 0ms / 0.2A @ 10ms

- -

AC

3A @ cosΦ 0.7

Contact signaling tripping of the YO2/YU – S52 This contact signals that the undervoltage (YU) or the shunt opening release (YO2) have been acti - vated. The contact is the same and depends on the service release mounted in the dedicated position. It is available for the XT7 only , with YU/YO2 installed in the dedicated slot. Auxiliary contact S52 doesn't read the tripping of the YO.

250V AC/DC contact

24V DC contact

Type

Switching

Switching 1mA @ 5V

Minimum load

100mA @ 24V

Breaking capacity DC

24V

-

0.1A

250V 250V

0.5A @ 0ms / 0.2A @ 10ms

- -

3A @ cos ϕ 0.7

AC