Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

7/28

— Signaling

Early Auxiliary Contacts – AUE Early closing auxiliary contacts: these allow the undervoltage release to be supplied before the main con- tacts close, in accordance with IEC 60204-1 and VDE 0113 standards. Early opening auxiliary contacts: these allow any electronic devices connected to the system to be disconnected in advance before the sys- tem is damaged by an overvoltage caused by the circuit-breaker opening. The early opening/closing auxil- iary contacts can be installed inside the direct and transmitted rotary handle operating mechanisms for all the SACE Tmax XT family circuit-breakers except for the XT7 (max two contacts @ 400V): • the cabled version includes 3.28ft long cables (AWG20 cable sections); • a dedicated code is available in the withdrawable version which includes the connector for the moving and fixed parts; For the XT7 with a lever operating mechanism, these are mounted directly on the circuit-breaker.

— Early Auxiliary Contacts

XT1

XT2

XT3

XT4

XT5

XT6

XT7

XT7 M

AUE closing AUE opening

- -

-

-

-

Early Auxiliary Contacts – AUE for XT7

400V/250V AC/DC contact

Type

Switching

Minimum load

100mA @ 24V

Breaking capacity DC

125V 250V 250V

0.3A

0.15A

AC

12A

3A

400V (1)

(1) Only ENEC approved