Tmax XT UL Catalogo [EN]

7/29

ACCESSOR I ES

Ready to close signaling contact - RTC The ready to close signaling contact – RTC – indicates that the circuit-breaker is ready to receive the clos- ing command and is available only for the XT7 M. The circuit-breaker is ready to close when the following conditions are fulfilled: • the circuit-breaker is open • the springs are loaded • there are no opening command or locks on the opening command • the circuit-breaker is reset following tripping of the Ekip protection trip unit.

250V AC/DC contact

24V DC contact

Type

Switching

Switching 1mA @ 5V

— Ready to close signaling contact

Minimum load

100mA @ 24V

Breaking capacity DC

24V

-

0.1A

250V 250V

0.5A @ 0ms / 0.2A @ 10ms

- -

3A @ cos ϕ 0.7

AC

Contact signaling loaded springs - S33 M/2 This contact is available for XT7 M only and signals the spring status of the circuit-breaker operating mech - anism. It is available in both 400V AC/DC and 24V DC versions and it is not included in the motor but must be order separately.

400V AC/DC contact Changeover contacts

24V DC contact

Type

Changeover contacts

Minimum load

100mA @ 24V

1mA @ 5V

Breaking capacity DC

24V

-

0.1A

125V 250V 250V

0.3A @ 10ms 0.15A @ 10ms 5A @ cos ϕ 1 5A @ cos ϕ 0.7 5A @ cos ϕ 0.3 3A @ cos ϕ 1 2A @ cos ϕ 0.7 1A @ cos ϕ 0.3

- - - - - - - -

AC

400V

Mechanical signaling of tripping the protection trip unit - TU Reset XT7 M circuit-breakers are always equipped with a mechanical device that signals the tripping status of the protection trip units. After the Ekip trip unit has been tripped due to an electrical fault, the signaling device clearly indicates the tripping status on the front of the circuit-breaker. The circuit-breaker can be reset only after the signaling pushbutton has been restored to its normal operating position.

— TU Reset