SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS
7/48
— Remote control
Electrical specifications
MOD
MOE and MOE-E
MOE XT6
XT1 – XT3
XT2 – XT4
XT5
[V] 24 DC
24 DC
24 DC
24 DC
[V] 48…60 DC 48…60 DC [V] 110…125 AC/DC 110…125 AC/DC 110…125 AC/DC 110…125 AC/DC [V] 220…250 AC/DC 220…250 AC/DC 220…250 AC/DC 220…250 AC/DC [V] 380…440 AC 380…440 AC 380 AC 380 AC [V] 480…525 AC 480…525 AC - - 48…60 DC 48…60 DC
Rated voltage, Un
[% Un] MIN=85% Un; MAX=110% Un
Operating voltage
Power absorbed on inrush Ps
[VA - W] ≤ 500
≤ 300
≤ 300
≤ 400
Power absorbed on continuing PC service Operating frequency
[VA - W] ≤ 300
≤ 150
≤ 150
≤ 150
[Hz] 50..60
50..60
CL →OP [s] < 0.1 OP → CL [s] < 0.1 TR → OP [s] < 0.1
< 1.5 < 0.1
1.5
3
< 0.08
< 0.08
Duration
< 3
< 3
< 5
N° operations 25000
25000 ≥ 150
20000 ≥ 100
10000 ≥ 100
Mechanical life
Minimum duration of electrical opening and closing command
[ms] ≥ 150
Motor – M Available on SACE Tmax XT7 M only, this motor automatically loads the closing springs of the circuit- breaker. The device automatically reloads the springs of the operating device when they are discharged and energized. In the event of a lack of power, the springs can be manually charged by using a dedicated lever on the operating device. The motor of the XT7 M can be equipped with an S33/M contact which signals the status of the springs that must be ordered separately.
Electrical specifications
Motor Operator XT7 M
[V] 24…30 AC/DC [V] 48…60 AC/DC [V] 100…130 AC/DC [V] 220…250 AC/DC [V] 380…415 AC
— Motor operator
Rated voltage, Un
[% Un] MIN=85% Un; MAX=110% Un
Operating voltage
[VA - W] 300
Power absorbed on inrush Ps
[ms] 200
Inrush time
[VA - W] 100
Power absorbed on continue Pc service
[Hz] 50..60
Operating frequency
[s] 8
Charging time