Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

7/48

— Remote control

Electrical specifications

MOD

MOE and MOE-E

MOE XT6

XT1 – XT3

XT2 – XT4

XT5

[V] 24 DC

24 DC

24 DC

24 DC

[V] 48…60 DC 48…60 DC [V] 110…125 AC/DC 110…125 AC/DC 110…125 AC/DC 110…125 AC/DC [V] 220…250 AC/DC 220…250 AC/DC 220…250 AC/DC 220…250 AC/DC [V] 380…440 AC 380…440 AC 380 AC 380 AC [V] 480…525 AC 480…525 AC - - 48…60 DC 48…60 DC

Rated voltage, Un

[% Un] MIN=85% Un; MAX=110% Un

Operating voltage

Power absorbed on inrush Ps

[VA - W] ≤ 500

≤ 300

≤ 300

≤ 400

Power absorbed on continuing PC service Operating frequency

[VA - W] ≤ 300

≤ 150

≤ 150

≤ 150

[Hz] 50..60

50..60

CL →OP [s] < 0.1 OP → CL [s] < 0.1 TR → OP [s] < 0.1

< 1.5 < 0.1

1.5

3

< 0.08

< 0.08

Duration

< 3

< 3

< 5

N° operations 25000

25000 ≥ 150

20000 ≥ 100

10000 ≥ 100

Mechanical life

Minimum duration of electrical opening and closing command

[ms] ≥ 150

Motor – M Available on SACE Tmax XT7 M only, this motor automatically loads the closing springs of the circuit- breaker. The device automatically reloads the springs of the operating device when they are discharged and energized. In the event of a lack of power, the springs can be manually charged by using a dedicated lever on the operating device. The motor of the XT7 M can be equipped with an S33/M contact which signals the status of the springs that must be ordered separately.

Electrical specifications

Motor Operator XT7 M

[V] 24…30 AC/DC [V] 48…60 AC/DC [V] 100…130 AC/DC [V] 220…250 AC/DC [V] 380…415 AC

— Motor operator

Rated voltage, Un

[% Un] MIN=85% Un; MAX=110% Un

Operating voltage

[VA - W] 300

Power absorbed on inrush Ps

[ms] 200

Inrush time

[VA - W] 100

Power absorbed on continue Pc service

[Hz] 50..60

Operating frequency

[s] 8

Charging time

Powered by