7/47
ACCESSOR I ES
Operating mode: Manual
Operating mode: Auto
I: ON
I: ON
Discharged springs
Discharged springs
OFF push-button on the motor
YO / YU / RC
YO / YU / RC
ON push- button from remote
OFF push-button from remote
ON push-button on the motor
O: OFF
O: OFF
Discharged springs
Discharged springs
RESET push-button from remote
recharge the springs
O: OFF
O: OFF
Charged Springs
Charged Springs
With the XT5 MOE and MOE-E and the XT6 MOE, it is possible to define some reset logic in order to charge the springs automatically once the circuit-breaker has tripped depending on the reset wiring diagram cho- sen. Three different options are available: • Auto Reset: the circuit-breaker is automatically reset after a trip (not due to the trip unit) and the springs are charged; • Remote Reset: it is possible to connect a push-button in order to charge the springs after a trip (not due to the trip unit); • Manual Reset: charging springs must be done manually after a trip. As explained in the motor circuit diagram, the auxiliary contact S51 must be properly connected to enable remote or automatic resetting. After a trip due to an overload or a short-circuit (trip unit), only a manual reset is permitted.
Manual Reset
Remote Reset
Auto Reset
Discharged springs
Discharged springs
Discharged springs
I: ON
I: ON
I: ON
YO / YU / TU
YO / YU
YO / YU
ON push- button from remote
ON push- button from remote
ON push- button from remote
Discharged springs
Discharged springs
Discharged springs
O: OFF
O: OFF
O: OFF
RESET push- button from remote
Automatic springs recharging
Springs recharged manually
Recharge the springs
Charged springs
Charged springs
O: OFF
O: OFF
O: OFF
Powered by FlippingBook