Tmax XT UL Catalogo [EN]

7/47

ACCESSOR I ES

Operating mode: Manual

Operating mode: Auto

I: ON

I: ON

Discharged springs

Discharged springs

OFF push-button on the motor

YO / YU / RC

YO / YU / RC

ON push- button from remote

OFF push-button from remote

ON push-button on the motor

O: OFF

O: OFF

Discharged springs

Discharged springs

RESET push-button from remote

recharge the springs

O: OFF

O: OFF

Charged Springs

Charged Springs

With the XT5 MOE and MOE-E and the XT6 MOE, it is possible to define some reset logic in order to charge the springs automatically once the circuit-breaker has tripped depending on the reset wiring diagram cho- sen. Three different options are available: • Auto Reset: the circuit-breaker is automatically reset after a trip (not due to the trip unit) and the springs are charged; • Remote Reset: it is possible to connect a push-button in order to charge the springs after a trip (not due to the trip unit); • Manual Reset: charging springs must be done manually after a trip. As explained in the motor circuit diagram, the auxiliary contact S51 must be properly connected to enable remote or automatic resetting. After a trip due to an overload or a short-circuit (trip unit), only a manual reset is permitted.

Manual Reset

Remote Reset

Auto Reset

Discharged springs

Discharged springs

Discharged springs

I: ON

I: ON

I: ON

YO / YU / TU

YO / YU

YO / YU

ON push- button from remote

ON push- button from remote

ON push- button from remote

Discharged springs

Discharged springs

Discharged springs

O: OFF

O: OFF

O: OFF

RESET push- button from remote

Automatic springs recharging

Springs recharged manually

Recharge the springs

Charged springs

Charged springs

O: OFF

O: OFF

O: OFF

Powered by