Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

7/56

— Interlocks and switching devices

Cable interlocks These interlock systems, for the Tmax XT7 and XT7 M, enable various opening and closing configurations to be obtained between two or three circuit-breakers. Four types of interlock configuration are available:

Type A Excludes the possibility of having two circuit-breakers in the closed position at the same time.

1

2



O

O

I

O





O

I

The mechanical interlocks offer multiple solutions for installation that simplify their integration into the switchgear. The interlocks can be mounted: • vertically VR • horizontally HR Maximum distance between two interlocked XT7 breakers is 2750mm in the horizontal configuration and 1000mm in the vertical one. Mechanical interlocks are not compatible with AUX 15Q and the lock for preventing door opening when the circuit-breaker is in the closed position (DLC) and mounted on the right side.