Tmax XT UL Catalogo [EN]

7/57

ACCESSOR I ES

Automatic network-generator transfer unit ATS021-ATS022 (1) The ATS (Automatic Transfer Switch) is a network-generator transfer unit used in installations where switching the main power line to an emergency line is required to ensure power supply to the loads in case of anomalies in the main line. The unit is able to manage the entire transfer procedure automatically and prepares the commands for carrying out the procedure manually as well. In the case of an anomaly in the main line voltage, in accordance with parameters set by the user, the open- ing of the circuit-breaker of the main line, the starting of the generator set (when provided) and the clos- ing of the emergency line can be carried out. In the same way, when the line is supplied back, the procedure of reverse transfer is controlled automatically. The new generation of the ATS (ATS021 and ATS022) offers the most advanced and complete solutions to guarantee service continuity. The ATS021 and ATS022 can be used with all the circuit-breakers as well as the molded case switches of the SACE Tmax XT family. The ATS021 and ATS022 devices have been designed to operate with a self-supply. The ATS022 unit also prepares the connection for the auxiliary power supply, which allows additional functions to be used. The ATS021 and ATS022 devices carry out the control of both the power supply lines and analyze: • phase unbalance; • frequency unbalance; • phase loss. Apart from the standard control functions, the ATS022 enables the following operations: • selection of the priority line; • control of a third circuit-breaker; • integration of the device in a supervision system with Modbus communication (an auxiliary power supply is needed); Typical applications include: power supply to UPS (Uninterrupted Power Supply) units, operating theaters and primary hospital services, emergency power supplies for civil buildings, airports, hotels, data banks and telecommunication systems, and the power supply of industrial lines for continuous processes. For the correct configuration, each circuit-breaker connected to the ATS021 or ATS022 must be fitted with

— ATS021

— ATS022

the following accessories: • a mechanical interlock; • a motorized control for opening and closing; • a key lock against manual operation for the motor operator;

• a signaling contact for the status (open/closed) and a signaling contact for tripping; • a contact for the racked-in position (in the case of a withdrawable version circuit-breaker).

(1) Devices described in this section (ATS) are not UL listed.

Powered by