Tmax XT UL Catalogo [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

7/58

— Interlocks and switching devices

ATS021

ATS022

General Auxiliary Power Supply

Not Required

Not Required (24-110V DC is required only for Modbus dialogue and 16 2/3 Hz system)

Rated Voltage, Un [VAC]

Max 480

Max 480

Frequency [Hz]

50, 60

16 2/3, 50, 60, 400 3.78x5.67x6.69 Door mounting DIN-rail mounting

Dimensions (HxLxD) [in]

3.78x5.67x6.69 Door mounting DIN-rail mounting

Type of installation

Operating Mode

Auto/Manual

Auto/Manual

Features Monitoring of the Normal and Emergency lines Controlling CBs of the Normal and Emergency lines

Generator set start-up

Generator set shutdown with adjustable delay

Bus-tie

– – – –

No-priority Line Modbus RS485

Display

Ambient conditions Operating temperature

-20…+60 °C

-20…+60 °C

Humidity

5% - 90% without condensation 5% - 90% without condensation

Operating thresholds Minimum voltage

-30%…-5%Un +5%…+30%Un -10%…+10%fn

-30%…-5%Un +5%…+30%Un -10%…+10%fn

Maximum voltage

Fixed frequency thresholds

Test Test Mode

Compliance with standards Electronic equipment for power installations

EN-IEC 50178 EN 50081-2 EN 50082-2 IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3

EN-IEC 50178 EN 50081-2 EN 50082-2 IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3

Electromagnetic compatibility

Environmental conditions