50% 150% — Ekip Touch/Hi-Touch Protection functions L S I I steady state start-up t I7 t7 I

t

The Ekip Touch/Hi-Touch can be customized with the protection functions required.

I4

t4

I

I

8 L – Overload (L - ANSI 49) This function is used for protection against overloads. It allows the setting of the trip threshold, trip time and pre-alarm threshold. Three different types of trip curves are available: 1. t = k/l 2 with an inverse long time; 2. IDMT in accordance with IEC 60255-151 for coordination with medium voltage protection, available ac -

t t

t

100% 200%

Extremely Inverse Very Inverse Standard Inverse

50% 150%

t

L

I7

I3

S

t7

I

I I

cording to Standard Inverse (SI), Very Inverse (VI) and Extremely Inverse (EI) curves; 3. With a t = k/l4 curve for better coordination with upstream circuit-breakers or fuses. S – Time-delayed overcurrent (S - ANSI 51 & 50TD)

I

I

t

t t

steady state

start-up

t

I7

t

UV This function is used to protect against selective short-circuits. If necessary, it can be disabled, or if needed, only the trip can be excluded keeping the alarm indication, to be used in installations where conti- nuity of service is required. With a constant trip time (t = k), or constant specific let through energy (t = k/l 2 ).

U8

t7

I4

I2

t2 t4

I

t8

I V

I

I

t

100% 200% steady state

t

start-up

t t t

I – Short-circuit This function is used for instantaneous protection against short-circuits. The trip threshold is adjustable and, if needed, the protection can be disabled.

50% 150%

L

t

I7 I3

I1

S

OV

U9

t1

I

t7

I I I V I

t8 9

I

t

100% 200%

t

steady state 50% 150%

G - Ground fault This function protects against earth faults. The trip threshold and trip time are adjustable. When needed, the protection can be disabled.

t t

L

start-up

S

I2 I4

f12

UF

I

t2 t4

I

I I I f

t12

Neutral protection This function is used to adjust the setting provided from protections L, S and I on the Neutral pole with a control factor which is different from the other phases. It is available with values at 50%, 100%, 150% or 200% of the phase currents. It can be disabled if necessary.

t

t t t t

100% 200%

50% 150%

L

I1

I3

I4

S

OF

t1

f13

t4

I

I

t13

I I f I

voltage unbalance 2I - Second protection against instantaneous overcurrent This function protects against the instantaneous short-circuit (e.g. I protection) and it is enabled with an activa- tion event (or command), that can be programmed by the user. It can be activated for different uses in three ways: • locally, directly on the Ekip display unit • locally, with a smartphone with the EPiC app via Bluetooth • locally, with a PC with the Ekip Connect program • remotely, via any Ekip Com module connected to the circuit-breaker • remotely, via a switch wired through an Ekip Signalling module. When active, the Ekip display unit will show a confirmation of the activation and a red LED alarm will flash on the diagnosis bar. senso ciclico Moreover, the second instantaneous tripping curve (also referred to as RELT - Reduced Energy Let- Through) is designed to mitigate arc flashes. This protection can be adjusted from 1.5 to 15 x In with a ma- ximum setting of 18kA. Easy activation and I/O assignment, including positive feedback, can be establi - shed using the RELT Ekip Signaling 2k-3 module.