Tmax XT UL Catalog - Ed. 2021

t7

I I

PROTECT ION TR I P UNI TS

3/37

t t

100% 200%

50% 150% steady state

start-up

L

S

I

I I

t t

100% 200%

50% 150%

L

I4

S

t4

I

I

MCR – Closing on Short-circuit This protection uses the same algorithm as the l protection, limiting the operation to a settable time win- dow starting from the closing of the circuit-breaker. The protection can be disabled, when needed. The function is active with an auxiliary supply.

t t

I3

I4

t4

I I

t t

Iinst This guarantees the integrity of the circuit-breaker and installation in the case of particularly high current va- lues requiring shorter reaction times than those provided by the instantaneous short-circuit protection. The protection cannot be disabled, and the tripping threshold and time are defined by ABB.

I3

I2

t2

I I

IU - Current unbalance (ANSI 46) This function protects against an unbalance between the currents of the single phases protected by the circuit-breaker.

t

t

I1

t1

I7

I2

t2

t7

I

I

Harmonic distortion This allows a control alarm to be activated for a distorted waveform. If enabled, an alarm is activated for waveform factors higher than 2.1.

t

t

steady state

I1 Distorted waveform: Base + 3rd Harmonic start-up

t1

240 V

0 V

3rd Harmonic (150 Hertz)

-240 V

I I

Base Sine Waveform (50 Hertz)

T - Temperature This protects the circuit-breaker against abnormal temperatures recorded by the unit. It is always active, and has two states, according to the temperature: • Warning: -25 < t < -20 or 70 < t < 85 Display off; Warning LED on @ 0.5Hz. • Alarm: t < -25 o t > 85 Display off; Alarm and Warning LEDs on @2Hz; Circuit-breaker opening command. Hardware Trip This protects against internal disconnections of the circuit-breaker. If enabled, a fault is signaled and an opening command is sent if one or more of the following events are detected: • Current sensors disconnected (phase or external if enabled) • Rating plug disconnected (only for XT5 and XT7) • Trip coil disconnected (only signaling) • Incompatibility between protection release and mainboard (only for XT7) • Internal problems with the release. Current thresholds This function enables the realization of four independent thresholds to be indicated to enable corrective actions before the overload L protection trips the circuit-breaker. For example, by disconnecting the loads controlled by an Ekip Signalling device positioned downstream of the circuit-breaker.

t

100% 200%

50% 150%

L

Set B

S

Set A

I

I

Trigger event

t t

IEC 60947-4-1 Table 2

I4

t4

I I

t t

I3

Ij/Is

ti/tj

I f