SACE ® TMAX XT ® UL/CSA LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS UL489 AND CSA C22.2 STANDARDS
2/80
— Tmax XT4 - Installation Installation for fixed circuit-breaker
Mounting on the backplate
— Key 1 Insulating plate 2 Overall dimension of optional wiring ducts 3 Phase separators 0.98"/25mm 4 Front carter compulsory for panel door distance ≤ 25mm/0.98"
140 (4P) 5.51
95.5 3.76
135 5.31
90.5 3.56
52.5 2.07
82.5 3.25
35 1.38
35 1.38
35 1.38
4
1 0.04
1 0.04
1.1Nm
45 1.77 100 3.94 105 (3P) 4.13
2 0.08
3 0.12
1 0.04
117 4.61
1
Fixing at 1.97"/50mm With standard flange
A [in/mm]
3p-4p 3.39/86
3p-4p 3.29/83.5 3p-4p 3.60/91.5
Without flange
With side connector for Ekip Touch trip units
— Key 1 Front terminals 2 Flange for 4p circuit- breaker (always supplied with 4p cb) 3 Flange for 3p circuit- breaker (always supplied with 3p cb) 7 Tightening torque 1.1Nm 8 Tightening torque 8Nm 9 Optional wiring duct 10 Phase separators 0.98"/25mm 11 Rear insulating plate for 3p version 12 Rear insulating plate for 4p version 15 Connection kit F/P IntBus/ExtNeut/Sel