Tmax XT UL Caratteristiche Tecniche [EN]

— TECHNICAL CHARACTER I STICS SACE Tmax XT UL/CSA Low voltage molded case circuit breakers for UL489 and CSA C22.2 Standards

Break new ground • Data and connectivity

• Ease of use and installation • Performance and protection • Safety and reliability

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

INSTALL AT ION

I NSTALLAT ION

— SACE Tmax XT The complete offering

OVER ALL DIMENS IONS

WI R I NG DI AGR AMS

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

INSTALL AT ION

1/1

— Installation

Installation environment

1/ 3 1/ 3 1/ 3 1/ 4 1/ 4

Temperature

Environmental conditions Electromagnetic compatibility

Degrees of protection

Installation position Temperature performance

1/ 5

Circuit-breakers with thermal-magnetic trip units Circuit-breaker with magnetic only or electronic trip units and switch- disconnectors

1/ 8

1/ 9

Power losses Insulation distances Enclosure dimensions

1/ 11 1/ 14

Minimum clearance between two side by side circuit-breakers Minimum clearance between two superimposed circuit-breakers

1/ 17

1/ 18

The first insulated anchor Special applications

1/ 20

Use of direct current apparatus Characteristic curves Example of curves reading

1/ 22 1/ 24 1/ 32 1/ 44

Trip curveswith thermal-magnetic trip unit Trip curveswith electronic trip unit EkipDip Trip curves with electronic trip unit Ekip Touch and Hi-Touch Specific let-through energy curves

1/ 54 1/ 59

Limiting curves

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/2

INSTALL AT ION

1/3

— Installation environment

Temperature The Tmax XT circuit-breakers can be used in environmental conditions where the ambient air temperature varies between -25°C and +70°C, and can be stored at temperatures between -40 °C and +70 °C. Circuit-breakers fitted with thermomagnetic trip units have their thermal element set for a reference tempe- rature. For temperatures other than the reference, a trip threshold variation must be taken into account. Electronic trip units do not undergo any variations in performance as the temperature varies, but, in the case of temperatures exceeding +40°C, the maximum setting for protection L (protection against overloads) must be reduced, as indicated in the derating graph, to take into account the heating phenomena which oc- cur in the copper parts of the circuit-breaker which the phase current passes through. For temperatures above +70°C the circuit-breaker performances are not guaranteed. Environmental conditions The Tmax XT circuit-breakers are designed to operate in environments with a pollution degree of 3 accor- ding to the IEC 60947-2 Standard classification. Altitude Up to an altitude of 2000m/6561 ft, the Tmax XT circuit-breakers do not undergo any alteration in their rated performances. As the altitude increases, the atmospheric properties are altered in terms of composition, dielectric resistance, cooling capacity and pressure. Therefore, some performance aspects of the circuit-bre- aker (e.g. the maximum rated operating voltage and the rated uninterrupted current) undergo derating.

Altitude

2000m/ 6561ft

3000m/ 9842ft

4000m/ 13123ft

5000m/ 16404ft

Rated employ voltage, Ue Rated uninterrupted current

[V AC] 600

540

468

408

% 100

98

93

90

Electromagnetic compatibility Protection is guaranteed in the presence of interference caused by electronic apparatus, atmospheric di- sturbances or electrical discharges by using the electronic trip units and the electronic residual current relea- ses. No interference with other electronic apparatus near the place of installation is generated either. This is in compliance with the IEC 60947-2 Annex B + Annex F Standards, European Directive No. 2014/30/EC re- garding EMC - electromagnetic compatibility and UL489 Standard.

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/4

— Installation environment

Degrees of protection The IP degree of the circuit-breaker can vary depending on the area considered and on the presence of acces- sories such as a motor or terminal cover. The following table indicates the degrees of protection guaranteed by Tmax XT circuit-breakers according to the prescriptions of the IEC 60529 Standard, in the different configurations. Furthermore, special kits are available to achieve IP54 with the MOE or RHD installed on the XT5, XT6 and XT7.

B C

A

B

With front Without front

With FLD With RHD

With RHE Motor operator MOD, MOE or MOE-E

Residual current devices

A

IP40

IP20

IP40 (1)

IP40 (1)

IP40 (1)(2)

IP30

IP40

(1) XT5 W - XT6 W: IP30 (2) XT5-XT6-XT7: IP65

Without TC

With HTC

With LTC

B C

IP20

IP40 IP40

IP40 IP30

NC

Protection kits for XT1 , XT2 XT3,XT4 XT5, XT6, XT7

RHE

RHD

MOE

IP54

-

-

-

IP54

IP54

Residual current RCQ020

Automatic Transfer Switch ATS021, ATS022

On front

IP41

IP40

Installation position It is possible to mount circuit-breakers in the fixed, plug-in or withdrawable version in horizontal, vertical or lying down positions without any derating of the rated characteristics.

INSTALL AT ION

1/5

— Temperature performance

Circuit-breakers with thermal-magnetic trip units The circuit-breakers fitted with thermal-magnetic trip units have the thermal element set for a reference temperature of +40°C. With the same setting, for temperatures other than +40°C there is a variation in the thermal trip threshold as indicated in the tables below.

XT1 - TMF In [A]

30°C

40°C

50°C

60°C

70°C

15 20 25 30 35 40 45 50 60 70 80 90

16 21 26 32 37 42 48 53 63 74 84 95

15 20 25 30 35 40 45 50 60 70 80 90

14 19 23 28 33 38 42 47 56 66 75 85 94

13 18 22 26 31 35 40 44 52 61 70 79 88 96

12 16 20 24 29 33 37 41 49 57 65 73 81 90

100 110 125

105 115 131

100 110 125

103 117

109

102

XT2 - TMF In [A]

30°C

40°C

50°C

60°C

70°C

15 20 25 30 35 40 50 60 70

16 21 26 32 37 42 53 63 74

15 20 25 30 35 40 50 60 70

14 19 23 28 32 37 47 56 66

13 17 22 26 31 35 43 52 61

12 16 20 24 28 32 40 49 57

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/6

— Temperature performance

XT3 - TMF In [A]

30°C

40°C

50°C

60°C

70°C

60 70 80 90

63 74 84 95

60 70 80 90

56 66 75 84 93

52 60 69 78 87 95

49 56 64 72 80 88

100 110 125 150 175 200 225

105 116 132 158 185 211 237

100 110 125 150 175 200 225

102 116 140 163 186 210

108 130 151 173 194

100 121 141 161 181

XT4 - TMF In [A]

30°C

40°C

50°C

60°C

70°C

25 30 35 40 50 60 70

27 34 37 43 54 64 75

25 30 35 40 50 60 70

23 25 32 37 46 56 65

21 23 30 34 42 51 58

19 20 26 30 39 45 51

XT2 - TMA

30°C

40°C

50°C

60°C

70°C

In [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

80 90

59 66 74 81 92

84 95

56 63 70 77 88

80 90

53 59 65 72 82

75 84 93

49 55 61 67 76

70 78 87 96

46 51 57 62 71

65 73 81 89

100 110 125

105 116 132

100 110 125

103 117

109

101

INSTALL AT ION

1/7

XT4 - TMF and TMA 30°C

40°C

50°C

60°C

70°C

In [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

80 90

60 67 74 83 94

86 95

56 63 70 77 88

80 90

52 60 67 71 81 98

74 86 95

46 54 60 65 74 90

66 77 85 92

41 47 53 59 67 85 98

58 68 75 84 95

100 110 125 150 175 200 225 250

106 118 134 158 184 210 241 262

100 110 125 150 175 200 225 250

101 115 141 166 190 208 240

105 128 153 175 190 230

110 129 147 168 183

105 123 140 158 175

122 140 160 170 220

116 133 146 168

107 123 133 161

112 119 154

XT5 - TMA

30°C

40°C

50°C

60°C

70°C

In [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

300 400 500 600

220 310 375 440

314 420 535 630

210 280 350 420

300 400 500 600

200 260 330 395

286 380 470 572

187 240 305 345

267 350 435 534

165 225 280 300

235 320 400 500

XT6 - TMA

30°C

40°C

50°C

60°C

70°C

In [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

600 800

459 603

655 861

420 560

600 800

373 501

533 716

358 467

512 668

245 310

490 620

XT5 - TMG

30°C

40°C

50°C

60°C

70°C

In [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

MIN [A]

MAX [A]

300 400 500 600

220 310 375 440

314 420 535 630

210 280 350 420

300 400 500 600

200 260 330 395

286 380 470 572

187 240 305 345

267 350 435 534

165 225 280 300

235 320 400 500

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/8

— Temperature performance

Circuit-breaker with magnetic only or electronic trip units and switch- disconnectors The electronic overcurrent trip units do not undergo any variations in performance as the temperature var- ies. However, even though heating does not affect the trip thresholds of the electronic trip units, in the case of temperatures exceeding +40°C it is advisable to reduce the maximum L (protection against overloads) setting to protect the copper parts of the circuit-breaker against high temperatures. The same considerations can be made for the switch-disconnectors and magnetic only circuit-breakers. The table below shows the maximum value at which, with terminals and lugs, the threshold of I1 of the over- current protection (L) must be set according to the ambient temperature.

40°C

50°C

60°C

70°C

Imax [A]

Imax [A]

Imax [A]

Imax [A]

XT1

F P F

M-MCS M-MCS

125 125 125 125 225 225 250 250 400 400 600 600 800 800 800 800

112 106 112 106 201 191 224 213 400 368 600 497 800 736 800 800

97 88 97 88

79 70 79 70

XT2

M-ELT-MCS

P/W M-ELT-MCS

XT3

F P F

M-MCS M-MCS

174 158 194 177 362 333 572 453 724 666 800 800 949 953 980 980

142 126 158 140 319 294 512 405 638 587 755 716 894 853 849 849

XT4

M-ELT-MCS

P/W M-ELT-MCS

XT5 400

F

M-ELT-MCS

P/W M-ELT-MCS

XT5 600

F

M-ELT-MCS

P/W M-ELT-MCS

XT6

F

ELT-MCS

W ELT-MCS

XT7 800

F

ELT-MCS

W ELT-MCS

XT7 1000

F

ELT-MCS

1000 1000 1200 1200

1000 1000 1095 1095

W ELT-MCS

XT7 1200

F

ELT-MCS

W ELT-MCS

INSTALL AT ION

1/9

Power losses To ensure service continuity of the plants, careful assessment of how to keep temperatures within accept- able levels is necessary to guarantee operation of all devices (e.g. by using forced ventilation in switchboards and installation rooms). The table below shows the dissipated power values per single pole at the rated current In for each fixed cir- cuit-breaker used. The total maximum dissipated power for a circuit-breaker used at 50/60Hz is equal to the power per single pole multiplied by the number of poles.

Trip unit

In [A]

XT1 [W/pole]

XT2 [W/pole]

XT3 [W/pole]

XT4 [W/pole]

XT5 [W/pole]

XT6 [W/pole]

Thermomagnetic trip units: TMF. TMA. TMG

15 20 25 30 35 40 45 50 60 70 80 90

1.3 1.8 2.0 1.8 2.0 2.6 3.0 3.7 3.9 3.7 4.8 5.7 7.0 8.3

1.1 1.6 1.8 2.3 2.8 3.7

- - - - - - - -

- -

2.7 3.9 4.4 4.5

-

-

4.1 4.4 4.4 5.8 6.6 8.1 8.8

4.7 4.8 5.4 5.5 6.0 6.2 6.7 7.4 7.8 8.9 9.1

3.9 3.7 4.8 4.5 5.6 5.8 6.6 6.9 7.9

100 110 125 150 160 175 200 225 250 300 400 500 600 800

10.7

11.4

- - - - - -

- - - - - -

10.1 13.2 14.4

11.9 13.3 16.4

-

15.4 24.1 33.5 46.0

30.6 54.2

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/10

— Temperature performance

Trip unit

In [A]

XT1 [W/pole]

XT2 [W/pole]

XT3 [W/pole]

XT4 [W/pole]

XT5 [W/pole]

XT6 [W/pole]

Electronic trip units: Ekip Dip. Ekip Touch

10 25 40 60

- - - - - - - - - -

0.1 0.8 0.7 1.5 4.2 6.6

- - - - - - - - - -

- -

0.6 1.3 3.5

100 125 150 200 225 250 300 400 600 800

-

- - - -

7.8

10.5 13.3 16.4

8

10.8

19 43

30

53.4

Magnetic only trip units: MA

3 7

1.4 3.2 1.1

3.7 9.3 6.4

- - - - - - - -

- - -

15 25 30 50 70 80

-

-

2.6

2.3 3.1 5.3 5.3 6.6

3.8

-

5

6.8

5.5 6.8 8.1

-

5.5 6.2 6.7 7.4 7.8 9.1

100 110 125 150 175 200 225 250 300 400 500

4.5 3.3 4.1 6.5

-

-

10.3

14

- - - - -

- - - - -

-

8.6

11.9 13.3 16.4 15.4 24.1 33.5

- -

15.4 24.1 33.5

Trip unit

In [A]

XT7- XT7 M [W/Pole]

Electronic trip units: Ekip Dip, Ekip Touch

600 800

14 24 37 53

1000 1200

Power losses give indication of the heat generated under specified conditions. Measurement of power losses is performed on new samples in free air (according to Annex G of IEC 60947-2). The measurement of resistance cannot be directly related to the power loss of the device and it is not the proper parameter to assess poor performance of the poles.

INSTALL AT ION

1/11

— Insulation distances

Enclosure dimensions XT1, XT2, XT3, XT4 , XT5, XT6 and XT7 circuit breakers are available both as standard version and as 100% rated version. Because of the additional heat generated bringing 100% of continuous current rating the use of specific 90°C rated wires sized per 75°C ampacity may be required.

Circuit-breaker dimensions (HxWxD) in/mm

XT1

5.12/130

3 (4 4p)/76.2 (101.6 4p)

2.75/70

XT2

5.12/130

3.54 (4.72 4p)/90 (120 4p)

3.25/82.5

XT3

5.9/150

4.13 (5.51 4p)/105 (140 4p) 2.75/70

XT4

6.3/160

4.13 (5.51 4p)/105 (140 4p) 3.25/82.5

XT5

8.07/205

5.51(7.32 4p)/140(186 4p)

4.05/103

XT6

10.55/268

8.27(11.02 4p)/210(280 4p) 4.07/103.5

XT7

10.55/268

8.27 (11.02 4p)/210 (280 4p) 6.57 (7.01) (3) /166 (178) (3)

(3) For XT7 M

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/12

— Insulation distances

AC-DC Minimum enclosure sizes for 80% rated fixed circuit-breakers (HxWxD)

XT1

Cubicle dimension (in/mm) for 3p fixed version: 14.57x8.50x2.85/370x216x72.5 (with rear terminals: 15x9.84x9.84/380x250x250) Cubicle dimension (in/mm) for 4p fixed version: 14.57x9.50x2.85/370x241x72.5 (with rear terminals: 15x10.82x9.84/380x275x250) Cubicle dimension (in/mm) for 3p fixed version: 12.2x7.09x3.29/310x180x83.5 (with rear terminals: 12.83x8.9x11.5/326x226x292) Cubicle dimension (in/mm) for 4p fixed version: 12.2x8.27x3.29/310x210x83.5 (with rear terminals: 12.83x10.08x11.5/326x256x292) Cubicle dimension (in/mm) for 3p fixed version: 14.57x8.54x2.83/370x217x72 (with rear terminals: 15.28x10.47x11.81/388x266x300) Cubicle dimension (in/mm) for 4p fixed version: 14.57x9.84x2.83/370x250x72 (with rear terminals: 15.28x11.85x11.81/388x301x300) Cubicle dimension (in/mm) for 3p fixed version: 14.96x7.68x3.29/380x195x83.5 (with rear terminals: 15.59x9.6x11.51/396x244x292.5) Cubicle dimension (in/mm) for 4p fixed version: 14.96x9.05x3.29/380x230x83.5 (with rear terminals: 15.59x10.98x11.51/396x279x292.5)

XT2

XT3

XT4

XT5

Cubicle dimension (in/mm) for 3p fixed version 19.92x15x6.02/506x381x153 (1) Cubicle dimension (in/mm) for 4p fixed version 19.92x16.83x6.02/506x427.5x153 (1) Cubicle dimension (in/mm) for 3p fixed version: 20.47x16.53x7.87/520x420x200 (1) Cubicle dimension (in/mm) for 4p fixed version: 20.47x19.29x7.87/520x490x200 (1) Cubicle dimension (in/mm) for 3p fixed version: 27.95x21.65x6.81/710x550x173 (1) Cubicle dimension (in/mm) for 4p fixed version: 27.95x24.4x6.81/710x620x173 (1)

XT6

XT7

(1) For installations with rear terminals please ask ABB

INSTALL AT ION

1/13

AC-DC Minimum enclosure sizes for 100% rated fixed circuit-breakers (HxWxD)

XT1

Suitable for continuous operation at 100-percent of rating up to 100A with 90°C wire. The wire size shall be based on the ampacity of 75°C rated wire Suitable for continuous operation at 100-percent of rating up to 100A with thermal magnetic trip unit and up to 125A with electronic trip unit Suitable for continuous operation at 100-percent of rating up to 225A with 90°C wire. The wire size shall be based on the ampacity of 75°C rated wire Suitable for continuous operation at 100-percent of rating up to 250A, with 90°C wire. The wire size shall be based on the ampacity of 75°C rated wire. With 75°C wire suitable for continuous operation at 100-percent of rating up to 200A with lugs FC CuAl only

Cubicle dimension (in/mm) for 3p fixed version: 14.57x8.50x2.85/370x216x72.5 (with rear terminals: 15x9.84x9.84/380x250x250) Cubicle dimension (in/mm) for 4p fixed version: 14.57x9.50x2.85/370x241x72.5 (with rear terminals: 15x10.82x9.84/380x275x250) Cubicle dimension (in/mm) for 3p fixed version: 12.2x7.09x3.29/310x180x83.5 (with rear terminals: 12.83x8.9x11.5/326x226x292) Cubicle dimension (in/mm) for 4p fixed version: 12.2x8.27x3.29/310x210x83.5 (with rear terminals: 12.83x10.08x11.5/326x256x292) Cubicle dimension (in/mm) for 3p fixed version: 14.57x8.54x2.83/370x217x72 (with rear terminals: 15.28x10.47x11.81/388x266x300) Cubicle dimension (in/mm) for 4p fixed version: 14.57x9.84x2.83/370x250x72 (with rear terminals: 15.28x11.85x11.81/388x301x300) Cubicle dimension (in/mm) for 3p fixed version: 14.96x7.68x3.29/380x195x83.5 (with rear terminals: 15.59x9.6x11.51/396x244x292.5) Cubicle dimension (in/mm) for 4p fixed version: 14.96x9.05x3.29/380x230x83.5 (with rear terminals: 15.59x10.98x11.51/396x279x292.5) Cubicle dimension (in/mm) for 3p fixed version, with vents for V-X versions: 19.92x15x6.02/506x381x153, vents: 2 x (4.33x6.9/110x175) (1) Cubicle dimension (in/mm) for 4p fixed version, with vents for V-X versions: 19.92x16.83x6.02/506x427.5x153, vents: 2 x (4.33x8.66/110x220) (1) Cubicle dimension (in/mm) for 3p V-X fixed versions without vents: 20.47x16.54x7.87/520x420x200 (1) Cubicle dimension (in/mm) for 4p V-X fixed versions without vents: 20.47x18.37x7.87/520x466.5x200 (1) Cubicle dimension (in/mm) for 3p fixed version, with vents: 19.92x15x6.02/506x381x153, vents: 2 x (4.33x6.9/110x175) (1) Cubicle dimension (in/mm) for 4p fixed version, with vents: 19.92x16.83x6.02/506x427.5x153, vents: 2 x (4.33x8.66/110x220) (1) Cubicle dimension (in/mm) for 3p fixed version without vents: 20.47x16.54x7.87/520x420x200 (1) Cubicle dimension (in/mm) for 4p fixed version without vents: 20.47x18.37x7.87/520x466.5x200 (1)

XT2

XT3

XT4

XT5 400 Suitable for continuous operation at 100-percent of rating up to 400A. For XT5 V-X 90°C wire needed, the wire size shall be based on the ampacity of 75°C rated wire

XT5 600 N-S-H-L versions suitable for continuous operation at 100-percent of rating up to 600A with 90C wire. The wire size shall be based on the ampacity of 75°C rated wire

XT6

Suitable for continuous operation at 100-percent of rating up to 800A with electronic trip unit and with 90°C wire. The wire size shall be based on the ampacity of 75°C rated wire Suitable for continuous operation at 100-percent of rating up to 1200A with 90°C wire. The wire size shall be based on the ampacity of 75°C rated wire

Cubicle dimension (in/mm) for 3p fixed version: 20.47x16.53x7.87/520x420x200 (1) Cubicle dimension (in/mm) for 4p fixed version: 20.47x19.29x7.87/520x490x200 (1) Cubicle dimension (in/mm) for 3p fixed version: 27.95x21.65x6.81/710x550x173 (1) Cubicle dimension (in/mm) for 4p fixed version: 27.95x24.4x6.81/710x620x173 (1)

XT7

(1) For installations with rear terminals please ask ABB

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/14

— Insulation distances

Minimum clearance between two side by side circuit-breakers This section gives the clearances to be observed for side by side installation of SACE Tmax XT circuit- break- ers in plants with voltages up to 600V. The following table shows the minimum center distance between two circuit-breakers of the same size mounted side by side. In case of XT2, XT3 and XT4 this installation is ob- tained by breaking the internal part of back insulating plate supplied with the breaker. Moreover in case of Tmax XT1 up to XT5 (1) , the values are valid only when they have an HTC or a phase separa- tor is inserted in the slot formed when placing the two fixed circuit-breakers side by side (see Fig.1 and Fig.2). For further details about installation, please see the related instructions provided with the circuit-breaker.

Circuit-breaker width (in/mm)

Centre distance I (in/mm)

3 poles 2.99/76 3.54/90 4.13/105 4.13/105 5.51/140 8.27/210 8.26/210

4 poles

3 poles

4 poles

XT1 XT2 XT3 XT4 XT5 XT6 XT7

4.02/102 4.72/120 5.51/140 5.51/140 7.32/186 11.02/280 11.02/280

2.99/76 3.54/90 4.13/105 4.13/105 5.51/140 8.27/210

4.02/102 4.72/120 5.51/140 5.51/140 7.32/186 11.02/280 11.02/280 (2)

8.26/210 (2)

(1) XT5: HTC or phase separator requested for installation voltage values Ue≥500V only (2) for installations with F terminals only. With other connections refer to distances fixed by dimensions of back insulating plates requested

INSTALL AT ION

1/15

— Note: Back insulating plate XT1...XT4 supplied with the breaker

XT2 circuit-breakers, plug-in execution with terminals EF, mounted side by side XT2 - XT4 (Ue>480V)

High terminal covers HTC

Phase separators

Phase separators XT2 circuit-breakers, plug-in execution with terminal EF, mounted side by side

XT2 circuit-br with terminals

— Fig. 1 Side by side XT1…XT5 (1) with HTC Fig. 2 Side by side XT1...XT5 (1) with phase separators

High terminal covers HTC

High terminal covers HTC

Phase separators

0

0

0

— Fig. 1

— Fig. 2

If the conditions on page 4 are not complied with, SACE Tmax XT circuit-breakers can be installed side by side with a minimum clearance D as shown in the following table:

If the conditions on page 4 are not complied with, SACE Tmax XT circuit-breakers can be installed side by side with a minimum clearance D as shown in the following table:

Circuit-breakers with fr nt extended spread terminals ES

Circuit-breakers with front extende

If the conditions on page 4 are not complied with, SACE Tmax XT circuit-breakers can be installed side by side with a minimum clearance D as shown in the following table: Circuit-breaker Terminals D [mm] XT1-XT3 F-P ES 35

Circuit-breakers with front extended spread terminals ES D

D

D [mm]

Circuit-breaker Terminals

XT1-XT3 F-P

ES

35

D

EF 35 Other types of terminals 25

EF 35 Other types of terminals 25

D [mm]

Circuit-breaker Terminals

ES XT2-XT4 F-W-P

XT2-XT4 F-W-P

ES

120

ES

120

XT1-XT3 F-P

35 35 Other types of terminals 25 EF

EF 35 Other types of terminals 25

EF 35 Other types of terminals 25

D

D

XT2-XT4 F-W-P

ES

120

EF 35 Other types of terminals 25 Here are some examples: Adjustable rear terminals R and low terminal covers LTC

Here are some examples: Adjustable rear terminals R and low terminal covers LTC

Circuit-breakers with front extended terminals EF

Circuit-breakers with front extende

D

D

D

Here are some examples: Adjustable rear terminals R and low terminal covers LTC

Circuit-breakers with front extended terminals EF

D

D

D

D

D

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/16

— Insulation distances

XT2 circuit-breakers, plug-in execution with terminals EF, mounted side by side

High terminal covers HTC

Phase separators

High terminal covers HTC

Phase separato

If the conditions written above are not fulfilled, SACE Tmax XT circuit-breakers can be installed side by side with a minimum clearance D as shown in the following table:

Circuit-breaker

Terminals

D [in/mm] 1.37/35 1.37/35 0.98/25 4.72/120

0

XT1-XT3 F-P

ES EF

0

XT2 circuit-breakers, plug-in execution with terminals EF, mounted side by side

HTC

Phase separators

Other types of terminals

XT2-XT4 F-P-W

ES EF

1.37/35 (Ue≤480V) 1.97/50 (Ue>480V) 0.98/25 (Ue≤480V) 1.57/40 (Ue>480V) Circuit-breakers with front extended spread terminals ES

Other types of terminals

XT5 F-P-W If the conditions on page 4 are not complied with, SACE Tmax XT circuit-breakers can be installed side by side with a minimum clearance D as shown in the following table:

If the conditions on page 4 are not complied with, SACE Tmax XT circuit-breakers can be installed side by side w minimum clearance D as shown in the following table:

ES EF

4.72/120

5.9/150

D

Other types of terminals

2/50

D [mm]

D [mm]

Circuit-breaker Terminals

XT6 F-W

ES EF

4.72/120

Circuit-breaker Terminals

XT1-XT3 F-P

ES

35

XT1-XT3 F-P

ES

35

5.9/150

EF 35 Other types of terminals 25

EF 35 Other types of terminals 25

Other types of terminals

2/50

XT2-XT4 F-W-P

XT7 F-W ES

120

ES EF

5.9/150 2.75/70

XT2-XT4 F-W-P

ES

120

EF 35 Other types of terminals 25

EF 35 Other types of terminals 25

Other types of terminals

0 fixed - 2.75/70 withdrawable

D

Here are some examples: Adjustable rea terminals R and low terminal cover LTC

Adjustable rear terminals R and low terminal covers LTC Here are some examples: Adjustable rear terminals R and low terminal covers LTC

Circuit-breakers with front extended spread terminals ES Circuit-bre e ith front extended spread terminals ES Circuit

Circuit-breakers with front extended terminals EF

page 4 are not complied with, SACE akers can be installed side by side with a D as shown in the following table:

kers with front extended terminals EF

D

D

D [mm]

minals

35 35 r types of terminals 25 120 35 r types of terminals 25

D

D

D

D

mples: inals R and low terminal covers LTC

ABB | SACE Tmax XT - Installation tips 5

Circuit-breakers with front extended terminals EF

D

D

ABB | SACE Tmax XT - Installation tips 5

INSTALL AT ION

1/17

Installation of SACE Tmax XT

Minimum clearance between two superimposed circuit-breakers This section gives the clearances H to meet for superimposed mounting of the SACE Tmax XT circuit- breakers in installations with voltages up to 600V. Verify that the bare bars or connection cables do not re- duce the recommended clearances. The distances given in the table refer to the maximum overall dimensions of the circuit-breakers in the dif- ferent versions (F/W/P), with terminals and metallic lugs of insulated cables included, for example. When superimposed circuit-breakers are different in size, the larger reference clearance should be considered.

Minimum clearance between two superimposed circuit-breakers This section gives the clearances H to comply with for superimposed mounting of SACE Tmax XT circuit-breakers in installations with voltage up to 690Vac. Verify that the bare bars or connection cables do not reduce the recommended clearances. Circuit-breaker XT1 XT2

execution (F/W/P), with terminals and, for example, meta lugs of insulated cables included.

Circuit-breaker

H [mm]

XT1

80

H [in/mm]

XT2

140

3.14/80

XT3

140

3.94/100 5.51/140

XT4

150

XT3 XT4

When the superimposed circuit-breakers are different in s (e.g. XT4 and XT2), the reference clearance to be conside is the longer one.

5.9/150

The distances given in the table are referred to the maximum overall dimensions of the circuit-breakers in the different XT5

7.88/200 7.09/180 7.09/180

XT6 XT7

In case of cables with metalli an insulating screen behind t metallic lugs (on the rear of th cuit-breaker) or high terminal are mandatory.

Metallic lug Insulated cable

H

H

H

In case of cables with metallic lugs, an insulating screen behind the metallic lugs (on the rear of the circuit- breaker) or high terminal covers is mandatory.

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/18

— Insulation distances

The first insulated anchor For the moulded-case circuit-breakers SACE Tmax XT1, XT2, XT3 and XT4, the gure below gives an example of the maximum recommended distance (in mm) within which the rst insulated anchor shall be positioned according to the highest admissible peak current value of the circuit-breaker The first insulated anchor For the Tmax XT molded-case circuit-breakers, the figure below giv s an exa ple of the maximum recom- mended distance (in mm) within which the first insulated anchor should be positioned according to the highest admissible peak current value of the circuit-breaker and according to the cross-sectional area of the cable. The maximum recommended distance is also valid for busbar connections. For further information and details circuit-breaker instruction manuals should be consulted. The first insulated anchor and to the cross-sectional area of the cable. The maximum recommended distance is valid also with busbar connections. For further information and details reference must be made to the circuit-breaker technical catalogues and instruction manuals. and to the cross-sectional area of the cable. The maximum recommended distance is valid also with busbar connections. For furth r infor ation and details reference must be made to the circuit-breaker technical catalogues and instruction manuals. a t the cross-sectional area of the cable. T e maxim recommende distance is valid also with busbar connections. For furt er informati an details reference must be made to the circuit-breaker tec ical catalogues and i struction manuals. and to the cros -sectional area of the cable. The maximum recommended distance is valid also with busbar con ections. For further information and details reference must be made to the circuit-breaker technical catalogu s and instructi n manuals. For the moulded-cas circuit-breakers SACE Tmax XT1, XT2, XT3 and XT4, the gure below gives an example of the maximum r commended distance (in mm) withi whic the rst insulated anchor shall be positioned according to the highest admissible peak current value of the circuit-breaker The fir t i s l ted anchor F r the moulded-case circuit-breakers SACE Tmax XT1, XT2, XT3 and XT4, the gure below gives an example of the aximum recommended distance (in mm) within which the rst insulated anchor shal be positione according to the ighest ad is ible peak c r e t val e of the circ it-breaker T e first ins late a c r For the moulded-case circuit-breakers SACE T ax XT1, X 2, XT3 and XT4, the gure below gives an example of the maximum recommended distance (in mm) within which the rst insulated anchor shall be positio ed according to the highest admis ible peak cur nt value of the circuit-break r SACE Tmax XT1 SACE Tmax XT2

SACE Tmax XT1 SACE Tmax XT1 SACE T ax XT1

SACE Tmax XT2 SACE Tmax XT2 SACE T ax XT2

16÷70 mm 2 (max 95 mm 2 ) 16÷70 m 2 (max 95 mm 2 ) 16÷70 m 2 (max 95 m 2 ) 16÷70 m 2 (max 95 2 )

16÷70 mm 2 16÷70 mm 2 16÷70 m 2 16÷70 m 2

SACE Tmax XT1

SACE Tmax XT2

2.5÷10 mm 2 2.5÷10 mm 2 2.5÷10 m 2 2.5÷10 m 2

2.5÷10 mm 2 2.5÷10 mm 2 2.5÷10 m 2.5÷10 m 2 2

SACE Tmax XT3 SACE Tmax XT3 SACE T ax XT3 SACE Tmax XT3

SACE Tmax XT4 SACE Tmax XT4 SACE T ax XT4 SACE Tmax XT4 SACE Tmax XT4

16÷120 mm 2 (max 185 mm 2 ) 16÷120 m 2 (max 185 mm 2 ) 16÷120 m 2 (max 185 16÷120 m 2 (max 185 m 2 ) 2 )

16÷120 mm 2 (max 185 mm 2 ) 16÷120 m 2 (max 185 mm 2 ) 16÷120 m 2 (max 185 m 2 ) 16÷120 m 2 (max 185 2 )

SACE Tmax XT3

2.5÷10 mm 2 2.5÷10 mm 2 2.5÷10 m 2 2.5÷10 m 2

(*) Value valid also with rear terminals (*) Value valid also with rear terminals (*) Value valid also with rear terminals (*) Value valid also with rear terminals

2.5÷10 mm 2

2.5÷10 m 2

2.5÷10 mm 2

INSTALL AT ION

1/19

16÷120 mm 2 (max 185 mm 2 ) The first insulated anchor For the moulded-case circuit-breakers SACE Tmax XT1, XT2, XT3 and XT4, the gure below gives an example of the maximum recommended distance (in mm) within which the rst insulated anchor shall be positioned according to the highest admissible peak current value of the circuit-breaker SACE Tmax XT3 SACE Tmax XT5

2.5÷10 mm 2 and to the cross-sectional area of the cable. The maxi um recommended distance is valid also with busbar connections. For further information and details reference must be made to the circuit-breaker technical catalogues and instruction manuals. 16÷120 mm 2 (max 185 mm 2 ) 16÷120 mm 2 (max 185 mm 2 ) SACE T

SACE Tmax XT3

SACE Tmax XT4

SACE Tmax XT6

SACE Tmax XT1

SACE Tmax XT2

16÷70 mm 2 (max 95 mm 2 )

16÷70 mm 2

2.5÷10 mm 2

2.5÷10 mm 2

(*) Value valid also with rear terminals

(*) Value valid also with rear terminals

SACE Tmax XT3

SACE Tmax XT4

ABB | SACE Tmax XT - Installatio

16÷120 mm 2 (max 185 mm 2 )

16÷120 mm 2 (max 185 mm 2 )

SACE Tmax XT7

2.5÷10 mm 2

(*) Value valid also with rear terminals

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/20

— Special applications

Use of direct current apparatus The thermal-magnetic trip units of the SACE Tmax XT circuit-breakers are suitable for use in direct current ap- plications and to obtain the number of poles in series needed to guarantee the required breaking capacity at the various operating voltages, following connection diagrams must be used.

Connection diagrams of poles in a grounded/ungrounded network

Grounded/ungrounded network Un

up to 250V DC

+ (-)

- (+)

+ (-)

- (+)

+ (-)

+ (-)

- (+)

LOAD

LOAD

- (+)

- (+)

+ (-)

LOAD

LOAD

LOAD

XT1 XT2 XT3 XT4 XT5 XT6

 (1)  (1)  (1)

  

(1) Ungrounded only

Un

up to 500V DC

+ (-)

- (+)

- (+)

+ (-)

- (+)

+ (-)

+ (-)

+ (-)

+ (-)

- (+)

+ (-)

- (+)

LOAD

LOAD

+ (-)

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

XT1

 (1)

XT2

 

XT3

 (1)

    (1)

XT4

 

XT5

XT6  (1) Ungrounded only

INSTALL AT ION

1/21

Un

up to 600V DC

+ (-)

+ (-)

- (+)

LOAD

LOAD

XT1 XT2 XT3 XT4

XT5

 (2)

XT6

(2) Grounded V-X versions only

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/22

— Characteristic curves Example of curves reading

Example 1 – XT3N 225 Trip curves for distribution (thermal magnetic trip unit)

Example 2 – XT2H 125 Specific let-through energy curves

These curves provide information about the tripping time of the thermal magnetic trip units.The red band indicates the hot trip times, that is with the breaker already loaded with its rated current once the overload has occurred. The blue band gives the cold trip times, that is with no current flowing into the breaker before the fault. The curves are assumed at reference air ambient temperature of 40°C and considering three phase overload with symmetri- cal and equilibrated currents. Let us consider an XT3N TMF In = 225A circuit-breaker. Based on the occurrence of the overload, either with the cir- cuit-breaker at thermal regime, or not, thermal protection tripping varies considerably. For example, for an overload current 3xI1, the trip time is be- tween 152.7s and 40.2s for cold tripping and between 40.2s and 6.9s for hot tripping. For fault current values higher than 225A, the circuit- breaker trips with the instantaneous magnetic protection I3.

This figure figure shows a sample graph of the specific let- through energy of the XT2H 125 circuit-breaker at a voltage of 220/230V. The prospective symmetrical short-circuit current is indicated on the x-axis, whereas the values of the specific let-through energy expressed in A2s are shown on the y-axis. The circuit-breaker lets through a value of I2t equal to 0.42 · 10^6 · A2s relative to a short-circuit current of 14kA.

I 2 t [10 6 A 2 s]

t [s]

10

10 4

10 3

152.7 s

10 2

1

40.2 s

10

6.9 s

14 kA

1

10 -1

3 x I 1

10 -1

10 -2

10 -2

10

1

x I 1 10 2

10 -1

10

1

10 3

10 2

x I rms [kA]

INSTALL AT ION

1/23

Example 3 – XT2L 125 Limitation curves

The figure at right gives the trend of the limitation curves of the XT2L 125 In = 125A circuit-breaker. The effective value of the prospective symmetrical short-cir- cuit current is given on the x-axis of the diagram, whereas the peak value corresponding to the prospective short-circuit cur- rent is indicated on the y-axis. For a value current of 22kA, the XT2L 125 circuit breaker with a thermomagnetic trip unit In = 125A limits the peak prospective short-current current to 18kA at a voltage of 600V.

Ip [kA]

10 3

10 2

18 kA

10

1

10

1

10 3

10 2

x I rms [kA]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/24

— Characteristic curves Trip curves with thermal magnetic trip unit

Trip curves for distribution XT1 125 TMF In=15..30A

XT1 125 TMF In=35...50A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

In=15A

In=35A

10 -1

10 -1

In=20A

In=40A

In=25A

In=45A

In=30A

In=50A

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT1 125 TMF In=60...110A

XT1 125 TMF In=125A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

I 3 =10xIn

I 3 =10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

INSTALL AT ION

1/25

XT2 125 TMF In=15...30A

XT2 125 TMF In=35...50A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

In=30A In=25A In=20A In=15A

10 -1

10 -1

In=40/50A In=35A

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT2 125 TMF In=60...70A

XT2 125 TMA In=80...100A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

I 3 =10xIn

I 3 =5...10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/26

— Characteristic curves Trip curves with thermal magnetic trip unit

XT2 125 TMA In=110...125A

XT3 225 TMF In=60..100A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

I 3 =10xIn

10 -1

10 -1

I 3 =5...10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT3 250 TMF In=110..150A

XT3 250 TMF In=175..225A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

I 3 =10xIn

I 3 =10xIn

10 -1

10 -1

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

INSTALL AT ION

1/27

XT4 250 TMF In=25...50A

XT4 250 TMF In=60...70A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

In=25A

In=30A

10 -1

10 -1

In=40...50A In=35A

I3=10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT4 250 TMF In=80...100A

XT4 250 TMF In=110...150A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/28

— Characteristic curves Trip curves with thermal magnetic trip unit

XT4 250 TMF In=175...225A

XT4 250 TMF In=250A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT4 250 TMA In=80...100A

XT4 250 TMA In=110...150A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

I3=5...10xIn

I3=5...10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

INSTALL AT ION

1/29

XT4 250 TMA In=175...225A

XT4 250 TMA In=250A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

I3=5...10xIn

I3=5...10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT5 400/600 TMA In=300...600A

XT6 800 TMA In=600...800A

t [s]

t [s]

10 4

10 4

10 3

10 3

10 2

10 2

10

10

1

1

10 -1

10 -1

I3=5...10xIn

I3=5...10xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/30

— Characteristic curves Trip curves with thermal magnetic trip unit

Trip curves for motor protection XT1 125 MA In=3...125A

XT2 125 MA In=3...100A

t [s]

t [s]

10 4

10 4

10 3

10 3

Overload limit

Overload limit

10 2

10 2

10

10

1

1

I3=3...11xIn (In=15...125A)

I3=4...11xIn (In=3...7A) I3=3...11xIn (In=15...100A)

10 -1

10 -1

I3=4...11xIn (In=3...7A)

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

XT2 125 MA In=125A

XT3 225 MA In=100...200A

t [s]

t [s]

10 4

10 4

10 3

10 3

Overload limit

Overload limit

10 2

10 2

10

10

1

1

I3=5...10xIn (In=125A)

I3=6...12xIn (In=100...200A)

10 -1

10 -1

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

INSTALL AT ION

1/31

XT4 250 MA 25...50A

XT4 250 MA 80...250A

t [s]

t [s]

10 4

10 4

10 3

10 3

Overload limit

Overload limit

10 2

10 2

10

10

1

1

I3=3...11xIn (In=25...50A)

I3=5...10xIn (In=80...250A)

10 -1

10 -1

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

Trip curves for generator protection XT5 TMG 300...600A

XT5 250 MA 300...500A

t [s]

t [s]

10 4

10 4

10 3

10 3

Overload limit

10 2

10 2

10

10

1

1

I3=6...12xIn (In=300...500A)

10 -1

10 -1

I3=2,5...5xIn

10 -2

10 -2

10

10

1

1

x I 1 10 2

x I 1 10 2

10 -1

10 -1

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/32

— Characteristic curves Trip curves with electronic trip unit Ekip Dip

Trip curves for distribution XT2 Ekip LS/I L-I functions

XT2 Ekip LS/I L-S functions

t [s]

t [s]

10 4

10 4

0.4...1

0.4...1

1

1

0.4

0.4

1

10

10 3

10 3

1

1...10

1...10

10

10 2

10 2

10

10

10 2

10 2

1

1

10 -1

10 -1

10 -2

10 -2

10 -3

10 -3

x In 10

I [kA] 10

10

I [kA] 10

1

1

1

1

10 -1

10 -1

10 -1

10 -1

x In

XT2 Ekip LIG L-I functions

XT2 Ekip LIG G function

t [s]

t [s]

10 4

10 4

0.4...1

0.2...1

1

0.4

0.2

1

10 3

10 3

1

1...10

10

10 2

10 2

10

10

10 2

1

1

Inhibited for I>4 In

10 -1

10 -1

10 -2

10 -2

10 -3

10 -3

10 2

x In 10

I [kA] 10

10

1

1

1

10 -1

10 -1

10 -1

x In

Page 1 Page 2 Page 3 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Page 14 Page 15 Page 16 Page 17 Page 18 Page 19 Page 20 Page 21 Page 22 Page 23 Page 24 Page 25 Page 26 Page 27 Page 28 Page 29 Page 30 Page 31 Page 32 Page 33 Page 34 Page 35 Page 36 Page 37 Page 38 Page 39 Page 40 Page 41 Page 42 Page 43 Page 44 Page 45 Page 46 Page 47 Page 48 Page 49 Page 50 Page 51 Page 52 Page 53 Page 54 Page 55 Page 56 Page 57 Page 58 Page 59 Page 60 Page 61 Page 62 Page 63 Page 64 Page 65 Page 66 Page 67 Page 68 Page 69 Page 70 Page 71 Page 72 Page 73 Page 74 Page 75 Page 76 Page 77 Page 78 Page 79 Page 80 Page 81 Page 82 Page 83 Page 84 Page 85 Page 86 Page 87 Page 88 Page 89 Page 90 Page 91 Page 92 Page 93 Page 94 Page 95 Page 96 Page 97 Page 98 Page 99 Page 100 Page 101 Page 102 Page 103 Page 104 Page 105 Page 106 Page 107 Page 108 Page 109 Page 110 Page 111 Page 112 Page 113 Page 114 Page 115 Page 116 Page 117 Page 118 Page 119 Page 120 Page 121 Page 122 Page 123 Page 124 Page 125 Page 126 Page 127 Page 128 Page 129 Page 130 Page 131 Page 132 Page 133 Page 134 Page 135 Page 136 Page 137 Page 138 Page 139 Page 140 Page 141 Page 142 Page 143 Page 144 Page 145 Page 146 Page 147 Page 148 Page 149 Page 150 Page 151 Page 152 Page 153 Page 154 Page 155 Page 156 Page 157 Page 158 Page 159 Page 160 Page 161 Page 162 Page 163 Page 164 Page 165 Page 166 Page 167 Page 168 Page 169 Page 170 Page 171 Page 172 Page 173 Page 174 Page 175 Page 176 Page 177 Page 178 Page 179 Page 180 Page 181 Page 182 Page 183 Page 184 Page 185 Page 186 Page 187 Page 188 Page 189 Page 190 Page 191 Page 192 Page 193 Page 194 Page 195 Page 196 Page 197 Page 198 Page 199 Page 200