Tmax XT UL Caratteristiche Tecniche [EN]

SACE ® TMAX XT ® UL/CSA LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS UL489 AND CSA C22.2 STANDARDS

2/4

— Tmax XT1 - Installation Installation for fixed circuit-breaker

Mounting on the backplate

101.2 (4P) 3.98

83 3.27

— Key 1 Insulating plate

96 3.78

78 3.07

2 Overall dimension of optional wiring ducts 12.79"/325mm 3 Phase separators 0.98"/25mm 4 Front carter compulsory for panel door distance ≤ 0.98"/25mm

38.1 1.5

70 2.76

25 0.98

25 0.98

25 0.98

4

1 0.04

1 0.04

1 0.04

1.1Nm

45 1.77

A [in/mm]

3 0.12

2 0.08

71 2.8 76.2 (3P) 3.0

With standard flange

3p-4p 2.91/74 3p-4p 2.79/71 3p-4p 3.11/79

1 0.04

101 3.97

Without flange

1

Mounting on DIN 50022 rail

101.2 3.98

83.5 3.29

76.2 3.0

71.5 2.81

25 0.98

25 0.98

25 0.98

1.5 0.06

— Key 1 Mounting bracket 2 Overall dimension of optional wiring ducts 3 Phase separators 0.98"/25mm 4 Optional front cover for DIN rail 5 Insulating plate

1.1Nm

1 0.04

1 0.04

1 0.04

1 0.04

5

38.1 1.5

7.5 0.29

102.5 4.04