SACE Emax 2 UL [EL]

SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS

6/6

— Accessories for circuit breakers

Auxiliary position contacts - AUP (Fig. 02A/B) When the circuit breaker is a withdrawable version, the position of the mobile part can be signalled electrically by accessorizing the fixed part with one of the following signalling contact units:

Auxiliary position contacts (AUP)

E1.2

E2.2 … E6.2

- -

standard

6 auxiliary contacts 5 auxiliary contacts

digital signals

standard

- - -

digital signals

5 supplementary

standard

— Fig. 02-A

auxiliary contacts

digital signals

-

Maximum number of auxiliary position contacts that can be installed

6

10

Standard contact changeover contacts

Contact for digital signals

Type

changeover contacts

Minimum load

100mA @ 24V

1mA @ 5V

Breaking capacity DC

— Fig. 02-B

24V

-

0.1A

125V 250V 250V

0.3A @ 0ms 0.15A @ 0ms 5A @ cos ϕ 1 5A @ cos ϕ 0.7 5A @ cos ϕ 0.3 3A @ cos ϕ 1 2A @ cos ϕ 0.7 1A @ cos ϕ 0.3

- - - - - - - -

AC

400V

— Electrical diagram reference: figures 95, 96, 97

Ready to close signalling contact - RTC (Fig. 03) The ready to close signalling contact – RTC – indicates that the circuit-breaker is ready to receive the closing command. The circuit-breaker is ready to close when the following conditions have been met: • circuit-breaker open • springs loaded • no opening command or locks on the opening command • circuit-breaker reset following tripping of Ekip protection trip unit • YU energized.

Standard contact

Contact for digital signals

Type

Switching

Minimum load

100mA @ 24V

1mA @ 5V

Breaking capacity

24V

-

0.1

— Fig. 03

DC

250V 250V

0.5A @ 0ms / 0.2A 10ms

- -

3A @ cos ϕ 0.7

AC

— Electrical diagram reference: figure 71