SACE Emax 2 UL [EL]

SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS

6/18

— Accessories for circuit-breakers

Technical characteristics

ATS021

ATS022

General

Auxiliary supply voltage

Not required

Not required (24-110V DC is required only for Modbus communication and systems of 16 2/3 Hz)

Supply voltage, Un

Max 480V AC

Max 480V AC

Frequency, fn

50, 60 Hz

16 2/3, 50, 60, 400 Hz

Dimensions

H mm W mm D mm

96

96

144 170

144 170

H

W D

Type of installation

Installation on front of switchgear Installation on DIN rail

Installation on front of switchgear Installation on DIN rail

Operating mode

Automatic/Manual

Automatic/Manual

Characteristics

Monitoring of normal and emergency line Control of circuit-breakers on normal and emergency line Setting start-up of generator Setting switch-off of generator with settable time delay Third circuit-breaker

- - - -

Selection priority line

Modbus Rs485 communication

Display

Environmental conditions

Protection degree

IP20*

IP20*

Operating temperature

-20 … +60 °C

-20 … +60 °C

Humidity

5% - 90% without condensation 5% - 90% without condensation

Operating thresholds

Undervoltage

-30%… -5% Un +5%…+30% Un -10% / +10% fn

-30%… -5% Un +5%…+30% Un -10%… +10% fn

Overvoltage

Frequency thresholds Test Mode Mode Test Gen set

Tests

Standards

Electronic devices for use in electrical installations

EN-IEC 50178 EN 50081-2 EN 50082-2

EN-IEC 50178 EN 50081-2 EN 50082-2

Electromagnetic compatibility

Environmental conditions

IEC 68-2-1 IEC 68-2-2 IEC 68-2-3

IEC 68-2-1 IEC 68-2-2 IEC 68-2-3

Electrical diagram reference: figures 100,101 and 102. * IP54 available with 1SCA101001R1001 accessory