SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS
6/26
— Accessories for Ekip trip units
Ekip LCD interface (Fig. 37) The Ekip trip units can be supplied with LCD black and white display, equipped with dedicated pushbut- tons to easily interact with the circuit-breaker. This option is well suited for aggressive environments char- acterized by low temperatures, high humidity or the presence of dust and chemical agents. The Ekip LCD trip units share the same advanced features with the touchscreen trip units in terms of protections, mea- surements and accuracy levels. However, the LCD version is not equipped with the embedded Bluetooth antenna. Rating Plug (Fig. 38) The rating plugs are field interchangeable from the front on all trip units and enable the protection thresh- olds to be adjusted according to the actual rated current of the system. This function is particularly advantageous in installations that may require future expansion or in cases in which the power supplied needs to be limited temporarily (e.g. mobile Gen Set). The Overload (L) protec - tion function can be disabled at any time by using an L OFF version of the rating plug. There is a matching L OFF version for each standard version of rating plug.
— Fig. 37
— Fig. 38
Circuit-breaker
Rating plugs available (both in standard and L OFF versions)
E1.2
400-600-800-1000-1200
E1.2 250
100-200-250
E2.2
400-600-800-1000-1200-1600-2000
E2.2 250
100-200-250
E4.2 E6.2
400-600-800-1000-1200-1600-2000-2500-3200-3600
400-600-800-1000-1200-1600-2000-2500-3200-3600-4000-5000-6000
Special rating plugs are also available for differential protection against ground faults in combination with a suitable toroid to be installed externally.
Circuit-breaker
Rating plug available for Rc protection
E1.2
400-630-800-1250
E1.2 250
100-200-250
E2.2
400-630-800-1250-2000
E2.2 250
100-200-250
E4.2 / E6.2
400-630-800-1250-2000-3200-4000