— Circuit breaker

Temperature derating Under specific installation conditions, the circuit- breakers can operate at higher temperatures than the reference temperature of 40 °C. In this case the current-carrying capacity of the circuit- breaker may be lower than the rated current-carrying

capacity at the reference temperature requiring the application of the derating coefficients as shown. Percentage values refer to withdrawable and fixed circuit breaker. If not specified, all data refer to a copper according to IEC60947.

Emax 2 E1.2

Temperature [°C/°F] <40/104

45/113

50/122

55/131

60/140

65/149

70/158

E1.2 E1.2 E1.2 E1.2 E1.2

250 400 800

100% 100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

1000 1200

98%

96%

94%

91%

88%

84%

Emax 2 E2.2

Temperature [°C/°F] <40/104

45/113

50/122

55/131

60/140

65/149

70/158

E2.2 E2.2 E2.2 E2.2 E2.2 E2.2

250 400 800

100% 100% 100% 100% 100% 100%

100% 100% 100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

100% 100% 100% 100%

1200 1600 2000

98% 97%

94% 93%

90% 88%

84% 82%

78% 76%

Emax 2 E4.2

Temperature [°C/°F] <40/104

45/113

50/122

55/131

60/140

65/149

70/158

E4.2 E4.2 E4.2 E4.2 E4.2

800

100% 100% 100% 100% 100%

100% 100% 100%

100% 100% 100%

100% 100% 100%

100% 100% 100%

100% 100% 100%

100% 100% 100%

1600 2000 3200 3600

98% 98%

96% 95%

92% 92%

87% 88%

81% 85%

75% 81%

Emax 2 E6.2

Temperature [°C/°F] <40/104

45/113

50/122

55/131

60/140

65/149

70/158

E6.2 E6.2 E6.2

4000 5000 6000

100% 100% 100%

100%

100%

100%

100%

100%

100%

98% 97%

96% 94%

91% 91%

86% 88%

80% 84%

74% 81%