INSTALL AT ION
7/13
— Installation in switchgear
Position All SACE Emax 2 circuit breakers can be floor mounted in a vertical position inside the switch- gear compartment. The E1.2 circuit breaker can also be installed in a horizontal position and wall mounted. Conve- niently, the screens of the Ekip Touch and Hi-Touch versions rotate to a horizontal view for key data when the E1.2 is installed horizontally. Insulation distances and connection The circuit breakers can be connected to the main power system using the most common configura- tions and dimensions of copper bars.
Power supply The Emax 2 circuit breakers can be supplied, from either the upper or lower terminals. In the event a measurement module is present, in order to make use of all information when the circuit breaker is in the open position, the voltage sockets must be in- stalled on the power supply side.
Installation of live parts must ensure: • Minimum insulation distances between the phases
Rated insulation voltage Ui
Minimum distance [mm]
1000V
The use of phase barriers is recommended for fixed version circuit breakers used in voltages over 480V.
• Insulation distance of installation cubicle
Fixed circuit breakers
Drawout circuit breakers
Width
C - Height D - Depth Width
C - Height
D - Depth
3p
4P
3p
4P
E1.2
[mm] 250 [inch] 9.84 [mm] 400
322
382.5 130 15.05 5.11
280
350
440
252
12.67
11.02
13.77
17.32
9.92 355
E2.2
490
500
221
400
490
440
[inch] 15.74 19.29 19.68 8.7
15.74
19.29
17.32
13.97
E4.2
[mm] 500
620
500
221
500
620
440
355
[inch] 19.68 24.41
19.68 8.7
19.68
24.41 1020 40.16 1200 47.24
17.32
13.97
E6.2
[mm] 900
1020 500
221
900
440
355
[inch] 35.43 40.16 19.68 8.7
35.43
17.32
13.97
E6.2/f
[mm] - [inch] -
1200 500
221
- -
440
355
47.24 19.68 8.7
17.32
13.97
D
D
C
C
B A
B A