SACE Emax 2 UL [EL]

SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS

10/2

— Instructions for ordering

SACE Emax 2 configured circuit breaker/ switch disconnector order code breakdown

1 Z

2 2

3 H

4 F

5&6 UJ

7 A

E

4 9

10 8

11 N

12 B

13 E

14 A

15 A

16 O

17 Q

18 C

19 E

20 A

8

1 - Emax 2 Prefix

2 - Frame

OEM Versions

E1.2 E2.2 E4.2 E6.2 E6.2/f

Z L

3p

Standard AC version

1 A

2 B G

4

6

-

4p - N Left** 4p - N Right

Triple Certification (UL/IEC/CCC)

C

D

E K

M

ML Naval version (IEC)

F

H

J

9 S

800 - 900VAC version (IEC)

* ReliaGear LV SWG: Only 3P version ** Standard

Marine (UL1066 SA) ReliaGear Family

A Y

Emax 2 for ReliaGear LV SWG (UL1558) Emax 2 for ReliaGear LV SB (UL891)

3 - Short Circuit Rating / Version B C

N

S

H

V

L

X

kA @ 508V AC

42 42 42 42

- -

50

65

85 85

100

- - - -

- -

UL kA @ 635V AC IEC kA @ 440V AC IEC kA @ 690V AC

65 (1)

85/100 (4)

50 (1)

50 42

66

85 66

100

150 100

150 100

85/100 (3)

66 (2)

1) E1.2N = 42kA 2) E1.2N = 50kA

3) E2.2H and E4.2H = 85kA / E6.2H = 100kA 4) E2.V and E4.2V = 85kA / E6.2V = 100kA

4 - Frame Rating [A]

A L 250 400 800 1200 1600 2000 2500 3200 3600 4000 5000 6000 B C D E F G H Z J K M N Y 250 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 P Q R S T U V W X

UL

IEC

Powered by