SACE Emax 2 UL [EL]

SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS

3/32

— Technical characteristics for protection trip units Measurement functions

Instantaneous measurements

Parameters L1, L2, L3, Ne

Currents (RMS)

[A] [A] [V] [V]

Ground fault current (RMS) Phase-phase voltage (RMS) Phase-neutral voltage (RMS)

Ig

U12, U23, U31

U1, U2, U3

Phase sequence Frequency Active power Reactive power Apparent power

[Hz] [kW]

f

P1, P2, P3, Ptot Q1, Q2, Q3, Qtot S1, S2, S3, Stot

[kVAR] [KVA]

Power factor Peak factor

total

L1, L2, L3, Ne

Counters recorded from installation or from the last reset

Parameters

Active energy Reactive energy Apparent energy

[kWh]

Ep total, Ep positive, Ep negative Eq total, Ep positive, Ep negative

[kVARh] [KVAh]

Es total

Network Analyzer

Parameters

Hourly average voltage value

[V] [no]

- Umin= 0.75…0.95 x Un - Umax= 1.05…1.25 x Un - Events counter (nr. of events day by day in the last year plus the total events in the breaker's lifetime) - Umin= 0.75…0.95 x Un - Events counter (nr. of events day by day in the last year plus the total events in the breaker's lifetime) - Umax= 1,05…1,25 x Un - Events counter (nr. of events day by day in the last year plus the total events in the breaker's lifetime) - Umin1= 0.75…0.95 x Un - Umin2= 0.75…0.95 x Un - Umin3= 0.75…0.95 x Un - Umax1= 1.05…1.25 x Un - Umax2= 1.05…1.25 x Un - Events counter (nr. of events day by day in the last year plus the total events in the breaker's lifetime) - U neg. seq.= 0.02…0.10 x Un - Events counter (nr. of events day by day in the last year plus the total events in the breaker's lifetime) Current and Voltage - up to 50° - Alarm THD: 5…20% - Single harmonic alarm: 3...10% plus a count of minutes the harmonic has been exceeded

Short voltage interruptions

[no]

Short voltage spikes

[no]

Slow-voltage sags and swells

[no]

Voltage unbalance

[V] [no]

Harmonic analysis