SACE Emax 2 UL [EL]

SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS

3/34

— Technical characteristics for protection trip units Measurement functions

Record of values: of the parameter for each interval with time-stamping

Parameters I Min, I Max U Min, U max P Avg, P Max Q Avg, Q Max S Avg, S Max

Current: minimum and maximum

[A] [V]

Phase-phase voltage: minimum and maximum Active power: average and maximum Reactive power: average and maximum

[kW]

[kVAR]

Apparent power: average and maximum

[KVA]

Data logger: record of high sampling rate parameters

Parameters

Currents Voltages

[A] [V]

L1, L2, L3, Ne, Ig

U12, U23, U31

Sampling rate

[Hz]

1200-2400-4800-9600

Maximum recording duration

[s] [s]

13.6

Recording stop delay Number of registers

0-10s

[no]

2 independent

Information on trip and opening data: after a fault without auxiliary supply

Parameters

Type of protection tripped

eg. L, S, I, G, UV, OV

Fault values per phase

[A/V/Hz W/var]

eg. I1, I2, I3, neutral for S protection V12, V23, V32 for UV protection Date, time and progressive number

Time-stamping

Maintenance indicators Information on last 30 trips Information on last 200 events Number of mechanical operations (1)

Parameters

Type of protection, fault values and time-stamping

Type of event, time-stamping Can be associated to alarm

[no] [no]

Total number of trips Total operating time

[h]

Wear of contacts

[%]

Prealarm >80% Alarm = 100%

Date of maintenance operations performed Indication of maintenance operation needed Circuit-breaker I.D.

Last

Type of circuit breaker, assigned device name, serial number

Self-diagnosis

Parameters

Check of continuity of internal connections Failure of circuit breaker to open (ANSI 50BF)

Alarm due to disconnection: rating plug, sensors, trip coil Alarm following non-tripping of protection functions

Temperature (OT)

Prealarm and alarm for abnormal temperature

(1) with auxiliary supply present