t4
SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS
3/36
I
I
t t
I3 — Description of protection functions 50% 150% 100% 200% L S I
I I
t
t
I2
t
t2
I4
I7
t4
I
I
t7
Overload (L - ANSI 49) : available with three different types of trip curve: 1. t = k/l 2 with inverse long time;
t t
I
I1
t1
Thresholds can be fine tuned (for example 1A for circuit-breaker E1.2 1000A) and timings can be set to the second directly from the display. The settable pre-alarm indicates the set threshold is reached before the protection is tripped.
t
steady state
I3
start-up
I I
Time-delayed overcurrent (S - ANSI 51 & 50TD) : with constant tripping time (t = k), or with constant spe - cific let-through energy (t = k/l 2 ), this provides 15 current thresholds and 8 curves, for fine adjustment. The function can be excluded by setting the dip switch combination to “OFF”.
I
t
t
100% 200%
50% 150%
I2
L
t2
S
I
I
I
Thermal memory : for L and S protection functions, this is used to protect components, such as transform- ers, from overheating following an overload. The function, which can be enabled by the Ekip Connect soft- ware, adjusts the protection tripping time according to the length of time that has elapsed since the first overload, taking into account the amount of heat generated.
t t
I1
t1 L
t
cold curve
t
S
I4
I7
hot curve
t4
I I
t7
I
I
Instantaneous overcurrent (l - ANSI 50) : with tripping curve without intentional delay, it offers 15 tripping thresholds and can be excluded by setting the dip switch combination to “OFF”.
t t
steady state
I3
start-up
Closing on short-circuit (MCR): the protection uses the same algorithm of the protection l, limiting opera- tion to a settable time window from the closing of the circuit-breaker. The protection also can be disabled to protection l. The function is active with an auxiliary supply.
I I
t t t
Programmable instantaneous overcurrent (2I - ANSI 50): Second instantaneous tripping curve designed to mitigate against arc flashes (also referred to as RELT - Reduced Energy Let-Through). This protection can be adjusted from 1.5 to 15 x In, with a maximum setting of 18kA. The clearing time of the 2I protection is between 25 and 42ms at 60Hz (+5ms for 50Hz). Easy activation and I/O assignment, including positive feedback, can be implemented using the RELT Ekip Signalling 2K-3 module.
100% 200%
50% 150%
L
I3
I2
t2
S
I
I
I
I
t
Ground fault (G - ANSI 51N & 50NTD) : with tripping time independent of current (t = k) or constant specific let-through energy (t = k/l 2 ). The function can be excluded by setting the dip switch combination to “OFF”.
I1
t
t1
I4
t4
I
I
t
I3