Tmax XT UL Caratteristiche Tecniche [EN]

SACE TMAX XT UL/CSA LOW VOLTAGE MOLDED CASE C I RCUI T- BRE AKERS UL4 89 AND CSA C2 2 . 2 STANDARDS

1/8

— Temperature performance

Circuit-breaker with magnetic only or electronic trip units and switch- disconnectors The electronic overcurrent trip units do not undergo any variations in performance as the temperature var- ies. However, even though heating does not affect the trip thresholds of the electronic trip units, in the case of temperatures exceeding +40°C it is advisable to reduce the maximum L (protection against overloads) setting to protect the copper parts of the circuit-breaker against high temperatures. The same considerations can be made for the switch-disconnectors and magnetic only circuit-breakers. The table below shows the maximum value at which, with terminals and lugs, the threshold of I1 of the over- current protection (L) must be set according to the ambient temperature.

40°C

50°C

60°C

70°C

Imax [A]

Imax [A]

Imax [A]

Imax [A]

XT1

F P F

M-MCS M-MCS

125 125 125 125 225 225 250 250 400 400 600 600 800 800 800 800

112 106 112 106 201 191 224 213 400 368 600 497 800 736 800 800

97 88 97 88

79 70 79 70

XT2

M-ELT-MCS

P/W M-ELT-MCS

XT3

F P F

M-MCS M-MCS

174 158 194 177 362 333 572 453 724 666 800 800 949 953 980 980

142 126 158 140 319 294 512 405 638 587 755 716 894 853 849 849

XT4

M-ELT-MCS

P/W M-ELT-MCS

XT5 400

F

M-ELT-MCS

P/W M-ELT-MCS

XT5 600

F

M-ELT-MCS

P/W M-ELT-MCS

XT6

F

ELT-MCS

W ELT-MCS

XT7 800

F

ELT-MCS

W ELT-MCS

XT7 1000

F

ELT-MCS

1000 1000 1200 1200

1000 1000 1095 1095

W ELT-MCS

XT7 1200

F

ELT-MCS

W ELT-MCS