Tmax XT UL Caratteristiche Tecniche [EN]

INSTALL AT ION

1/5

— Temperature performance

Circuit-breakers with thermal-magnetic trip units The circuit-breakers fitted with thermal-magnetic trip units have the thermal element set for a reference temperature of +40°C. With the same setting, for temperatures other than +40°C there is a variation in the thermal trip threshold as indicated in the tables below.

XT1 - TMF In [A]

30°C

40°C

50°C

60°C

70°C

15 20 25 30 35 40 45 50 60 70 80 90

16 21 26 32 37 42 48 53 63 74 84 95

15 20 25 30 35 40 45 50 60 70 80 90

14 19 23 28 33 38 42 47 56 66 75 85 94

13 18 22 26 31 35 40 44 52 61 70 79 88 96

12 16 20 24 29 33 37 41 49 57 65 73 81 90

100 110 125

105 115 131

100 110 125

103 117

109

102

XT2 - TMF In [A]

30°C

40°C

50°C

60°C

70°C

15 20 25 30 35 40 50 60 70

16 21 26 32 37 42 53 63 74

15 20 25 30 35 40 50 60 70

14 19 23 28 32 37 47 56 66

13 17 22 26 31 35 43 52 61

12 16 20 24 28 32 40 49 57