SACE Emax 2 UL [EL]

SACE EMAX 2 NEW LOW VOLTAGE POWER C I RCUI T BRE AKERS TO ANS I C37 / UL 1066 / CSA STANDARDS

3/20

— Technical characteristics for protection trip units Protection functions

ABB Code ANSI/IEEE C37.2 Code

Function

Threshold

L

49

Overload protection

I1 = 0.4 - 0.42 - 0.45 - 0.47 - 0.5 - 0.52 - 0.55 - 0.57 - 0.6 - 0.62 - 0.65 - 0.67 - 0.7 - 0.72 - 0.75 - 0.77 - 0.8 - 0.82 - 0.85 - 0.87 - 0.9 - 0.92 - 0.95 - 0.97 - 1 x In

Thermal memory

Tolerance

trip between 1.05 and 1.2 x I1

S

50TD

Time-delayed overcurrent protection

I2 = 0.6 - 0.8 - 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4 - 5 - 6 - 7 - 8 - 9 - 10 x In

± 7% If ≤ 6 x In ± 10% If > 6 x In

Tolerance

51

Time-delayed overcurrent protection

I2 = 0.6 - 0.8 - 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4 - 5 - 6 - 7 - 8 - 9 - 10 x In

Thermal memory Tolerance

± 7% If ≤ 6 x In ± 10% If > 6 x In

I

50

Instantaneous overcurrent protection

I3= 1.5 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 x In

Tolerance

± 10%

G

50N TD

Ground fault protection

I4 (1) = 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 1 x In

Tolerance

± 7%

51N

Ground fault protection

I4 (1) = 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 1 x In

Tolerance

± 7%

(1) With Vaux all thresholds are available. Without Vaux minimum threshold is limited to: 0.3In (with In = 100A), 0.25In (with In = 400A) or 0.2In (for all other ratings) (2) The minimum trip time is 1s, regardless of the type of curve set (self-protection)

(3) Total clearing time is the sum of breaking time and trip time The tollerances above apply to trip units already powered by the main circuit with current flowing in at least two phases or an auxiliary power supply. In all other cases the following tollerance values apply

ABB Code

Trip threshold

Trip time

L S

Trip between 1.05 and 1.2 x I1

± 20% ± 20%

± 10% ± 15% ± 15%

≤ 60ms

I

G

± 20%