SACE Emax 2 UL [EL]

PROTECT ION TR I P UNI TS

3/21

Trip time 3)

Enable/Disable function

Pre Alarm Trip curve

Ekip Dip

with If = 3 I1, t1 = 3 - 12 - 24 - 36 - 48 - 72 - 108 - 144s (2)

Not allowed for UL Not allowed for UL

50 ... 90% I1 Step 1%

t = k / I 2

± 10% If ≤ 6 x In ± 20% If > 6 x In with If > I2, t2 = 0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8s The better of the two data: ± 10% t2 or ± 40 ms with If = 10 In, t2 = 0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8s

yes

-

t = k

yes yes

- -

t = k / I 2

± 15% If ≤ 6 x In ± 20% If > 6 x In Instantaneous

yes

-

t = k

≤ 30 ms with If > I4, t4 = 0.1 - 0.2 - 0.4 - 0.8s

yes

50 ... 90% I4 Step 1%

t = k

The better of the two data: ± 10% t4 or ± 40 ms with If = 3In, t4 = 0.1 - 0.2 - 0.4 - 0.8s

yes

50 ... 90% I4 Step 1%

t = k / I 2

± 15%