SACE Emax 2 UL [EL]

PROTECT ION TR I P UNI TS

3/43

n linear mode (restrained mode, two voltage limits are selected within which the protection is tripped at the set threshold (I20) reduced by the factor K corresponding to the measured voltage. The variation of the factor K is proportional to the voltage, and for voltages greater than the upper threshold (Uh), the thresh- old I20 applies, and for voltages below the lower threshold (UI), the minimum threshold (I20 * Ks) applies.

K

1

Ks

V

UI

Uh

Residual overvoltage (RV – ANSI 59N) : with constant trip time (t = k), helps protect against insulation loss in systems with insulated neutral or with grounded neutral with impedance.

2

V23

V12

α α

1

3

V31

Loss of field or reverse reactive power (RQ – ANSI 40 or 32RQ) : with constant trip time (t = k), the circuit breaker tripped when the total reactive power absorbed by the generator exceeds the set threshold. The constant threshold (k=0) or a function of the delivered active power of the generator (k≠0) can be selected.

Q

P

TRIP

Reactive overpower (OQ – ANSI 32OF) : with constant trip time (t = k), the function is tripped when reactive power exceeds the set threshold in the generator to network direction.

t

Q27

t27

Q

Active overpower (OP – ANSI 32OF) : with constant trip time (t = k), the function is tripped when the active power exceeds the threshold set in the delivering direction of the generator.

t

P26

t26

P

Active underpower (UP – ANSI 32LF ): with constant trip time (t = k), the function is tripped when the active power delivered by the generator is lower than the set threshold. The protection can be temporarily dis- abled in order to manage the start-up phase, by setting a time window from the closing of the circuit breaker, by using an electrical signal or via incoming communication to a relay.

t

P23

t23

P