— Description of protection functions

Rate of change of frequency (ROCOF – ANSI 81R) : enables both positive and negative frequency variations to be rapidly detected . The protection is constant and is tripped when the frequency variation in Hz/s is greater than the set threshold.

f(Hz)

frequency after failure

failure

50/60Hz

frequency after failure

Time

Second protection against voltage controlled overcurrent protection (S2(V) - ANSI 51V) : available in ad- dition to the protection S(V), enables total selectivity to be achieved in all installations.

t

1

Ks

t21

Ks

t20

I

KsxI20

I21 I20

KsxI21

Second protection against loss of field or reverse reactive power (RQ – ANSI 40 or 32R) : enables the gen- erator’s de-energization curve to be followed very accurately, thereby avoiding any unnecessary disconnec- tion.

Q

kq kq2

P

Q25

Q24